Nominal current IN
max. 10 mA (at 5 V DC)
max. 500 mA (at 24 V DC)
Test voltage: 5 V supply of the local bus (UBus) / 24 V supply (I/Os)
Test voltage: 5 V supply of the local bus (UBus) / functional ground
Note on dimensions
The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715).
Connection method
Bus base module
Push-in connection
Required configuration data
Operating mode
PWM, pulse generator, push-pull output
Nominal output voltage
24 V (U<sub>O</sub> - 1.1 V)
5 V DC
Nominal current I<sub>N</sub>
max. 10 mA (at 5 V DC)
max. 500 mA (at 24 V DC)
Nominal load, ohmic
max. 12 W (at 24 V DC nominal voltage)
max. 50 mW (at 5 V DC nominal voltage)
Nominal load, inductive
max. 12 VA (at 24 V DC nominal voltage)
max. 50 mVA (at 5 V DC nominal voltage)
Nominal load, lamp
max. 6 W (at nominal voltage)
Short-circuit current
typ. 2.2 A (for approx. 1.2 µs, auto-retry after approx. 40 µs, 24 V output)
typ. 24 mA (5 V output)
Transient surge protection
Mounting position
any (no temperature derating)
Scope of supply
including bus base module and Axioline F connectors
Overvoltage category
II (IEC 60664-1, EN 60664-1)
Pollution degree
2 (IEC 60664-1, EN 60664-1)
Maximum power dissipation for nominal condition
Supply voltage
24 V DC
5 V DC (via bus base module)
Supply voltage range
19.2 V DC ... 30 V DC including all tolerances, including ripple
Current consumption
typ. 30 mA (internal current consumption)
Protective circuit
Surge protection; electronic (35 V, 0.5 s)
Test voltage: 5 V supply of the local bus / 24 V supply (I/Os)
Test voltage: 5 V supply of the local bus (U<sub>Bus</sub>) / functional ground
Test voltage: 24 V supply (I/O) / functional ground
Note on the connection method
Please observe the information provided on conductor cross-sections in the “Axioline F: system and installation” user manual.
Conductor cross-section, rigid