Typ. starting time with Us
< 200 ms (with U<sub>s</sub> when controlled via A1)
Rated control circuit supply voltage US
19.2 V DC ... 30 V DC
24 V DC -20 % / +25 % (provide external protection)
Rated control supply current IS
Application
Emergency stop
Light grid
Safety door
Safety shut-off mats
Typical response time
< 175 ms (manual, monitored start)
< 200 ms (automatic start)
Typ. starting time with U<sub>s</sub>
< 200 ms (with U<sub>s</sub> when controlled via A1)
Response time
< 10 ms (Take the extension of the response time into consideration if you switch several devices in sequence.)
Recovery time
100 ms (Availability time after activating the sensor circuit during manual start)
250 ms (following demand of the safety function)
Start pulse length
min. 250 ms (manual start)
Maximum power dissipation for nominal condition
3.1 W (U<sub>B</sub> = 30 V , I<sub>L1</sub> = I<sub>L2</sub> = 2.4 A)
Rated surge voltage/insulation
See data sheet, section “Insulation coordination”.
Rated control circuit supply voltage U<sub>S</sub>
19.2 V DC ... 30 V DC
24 V DC -20 % / +25 % (provide external protection)
Rated control supply current I<sub>S</sub>
Power consumption at U<sub>S</sub>
Inrush current
< 10 mA (typ. with U<sub>S</sub> at S10/S12, Δt = 500 µs)
< 10 mA (typ. with U<sub>S</sub>, Δt < 100 ms)
< 10 mA (Δt = 500 µs)
< 5 A (Δt = 200 µs at U<sub>s</sub>)
> -5 mA (typ. with U<sub>S</sub> at S22, Δt = 500 µs)
max. 4.8 A (Δt = 10 ms)
Filter time
1 ms (For the logic. At A1 in the event of voltage dips at U<sub>s </sub>)
Deactivate the switch-on pulses for safety applications.
Does not apply for S22
max. 1.5 ms (Test pulse width of low test pulses)
Test pulse rate = 5 x Test pulse width
Protective circuit
Freewheeling circuit for inductive loads
Parallel protection against polarity reversal; Suppressor diode (Provide external fuse protection, see safety notes. Fuse type: 5 AT)
Suppressor diode
Description of the input
IEC 61131-2 type 3
IEC 61131-2 type 3 (S10, S12) PNP (S22)
non-safety-related
NPN
safety-related
safety-related sensor inputs
Input voltage range "0" signal
0 V DC ... 5 V DC
0 V DC ... 5 V DC (S10, S12)
S22 open
Input voltage range "1" signal
0 V ... 0 V (S22)
11 V DC ... 30 V DC
11 V DC ... 30 V DC (S10, S12)
19.2 V DC ... 30 V DC
Input current range "0" signal
0 mA ... 2 mA
0 mA ... 2 mA (S10, S12)
Max. permissible overall conductor resistance
Current consumption
-4 mA (S22)
< 5 mA (typ. with U<sub>S</sub> at S35)
< 7 mA (typ. with U<sub>S</sub> at S34)
4 mA (S10, S12)
7 mA
Output description
non-safety-related
PNP
PNP, IEC 61131-2 Type 2
Safety-related digital outputs
Output voltage
≥ 23 V DC (U<sub>s</sub> - 1 V)
Leakage current
max. 1 mA (in the safe state)
Max. capacitive load
max. 10 µF (2.4 A load)
max. 4.7 µF (1 A load)
Limitation of the voltage induced on circuit interruption
Switching frequency
1 Hz (Resistive, inductive, capacitive)
Output voltage when switched off
< 5 V DC (in the safe state)
Test pulses
< 1 ms (Test pulse width of low test pulses)