Amount of process data (Input/output data)
max. 128 kByte (Input and output data)
Protection class
III (IEC 61140, EN 61140, VDE 0140-1)
Pollution degree
2 (when installed in a control cabinet or housing with IP54 degree of protection or higher)
Amount of process data ()
max. 128 kByte (Input and output data)
Device function
PROFINET controller, PROFINET device
Number of supported devices
Supported functions
Automatic device replacement
Parameterizable alarm and startup behavior
Topology detection
Device ID
014A<sub>hex</sub> / 176<sub>dez</sub>
Vendor ID
00B0<sub>hex</sub> / 176<sub>dez</sub>
Programming languages supported
C#
C++
Function block diagram (FBD)
Java
Ladder diagram (LD)
Python®
Simulink®
Structured text (ST)
Symbolic flowchart (SFC)
Power consumption
max. 35 W (With fan module)
typ. 25 W (Without fan module)
Maximum power dissipation for nominal condition
max. 35 W (With fan module)
typ. 25 W (Without fan module)
Supply voltage range
19.2 V DC ... 30 V DC (including ripple (3.6 V<sub>PP</sub>))
Power supply connection
Screw terminal blocks, plug-in
Typical current consumption
Realtime clock
integrated (capacitive buffering)
Description realtime clock
1.73 s/day = 20 ppm at 25 °C
Conductor cross-section, rigid
Conductor cross-section, flexible
Conductor cross-section AWG
Connection method
RJ45 jack
USB type A, male connector
Note on the connection method
Auto negotiation and auto crossing, auto polarity exchange
Transmission speed
10/100 Mbps (LAN3.1/LAN3.2 (internally switched), half duplex or full duplex)
10/100/1000 Mbps (LAN 1/LAN 2, half duplex or full duplex)
Width / Height / Depth
122 mm / 182 mm / 173 mm (without fan module)
122 mm / 220 mm / 173 mm (With fan module)
Safety Integrity Level (SIL)
Safety Integrity Level Claim Limit (SIL CL)
Degree of protection
IP20 (Manufacturers declaration, not evaluated by UL)
Ambient temperature (operation)
0 °C ... 50 °C 3000 m ... 4000 m above mean sea level (With fan module only)
0 °C ... 55 °C 2000 m ... 3000 m above mean sea level (With fan module only)
0 °C ... 60 °C up to 2000 m above mean sea level (from 40 °C only with fan module)
Ambient temperature (storage/transport)