Input voltage
120 V AC
230 V AC
24 V DC
Nominal output current (IN)
2.17 A (230 V AC)
4.17 A (120 V AC)
Nominal input voltage range
Typical national grid voltage
Voltage type of supply voltage
Frequency range (f<sub>N</sub>)
Current consumption
19 A (24 V DC)
2.86 A (240 V AC)
6.9 A (100 V AC)
Efficiency
> 97 % (100 % load, with charged energy storage)
~ 87 % (100 % load )
Overload capability Mains operation
in accordance with internal fuse
Overload capability Battery operation
105 % (permanent)
120 % ... 150 % (20 s / 5 s, then shutdown)
Output voltage
120 V AC
120 V AC ±2 %
230 V AC
230 V AC ±2 %
24 V
Nominal output current (I<sub>N</sub>)
2.17 A (230 V AC)
4.17 A (120 V AC)
Maximum no-load power dissipation
approx. 23 W (120 V AC)
approx. 24 W (230 V AC)
typ. 10 W (230 V AC)
typ. 9 W (120 V AC)
Power loss nominal load max.
approx. 54 W (230 V AC)
approx. 57 W (120 V AC)
typ. 10 W (120 V AC)
typ. 11 W (230 V AC)
Nominal output frequency
±0.5 % (self-guided)
±5 % (grid-guided)
50 Hz
50 Hz ±5 Hz
60 Hz
60 Hz ±5 Hz
Total harmonic distortion factor (THD)
< 3 % (linear load)
< 8 % (non-linear load)
Electronic current limitation
> 2,5 x I<sub>N</sub> (> 200 ms)
Deep discharge protection
20 V DC ... 24 V DC (can be parameterized)
Nominal capacity range
3.4 Ah ... 200 Ah (5x 40 Ah)
End-of-charge voltage
24 V DC ... 31 V DC (temperature compensated)
Battery technology
VRLA, VRLA-WTR, LI-ION (see section: Ordering data)
Charge characteristic curve
Connection method
MINI-USB Type B
Screw connection
flexible
0.2 mm² ... 1.5 mm²
0.2 mm² ... 4 mm²
flexible with ferrule without plastic sleeve
0.2 mm² ... 1.5 mm²
0.2 mm² ... 4 mm²
flexible with ferrule with plastic sleeve
0.2 mm² ... 1.5 mm²
0.2 mm² ... 4 mm²
rigid
0.2 mm² ... 1.5 mm²
0.2 mm² ... 6 mm²