Inrush current integral (I2t)
Supply system configuration
Star network (TN, TT, IT (PE))
Nominal input voltage range
100 V AC ... 240 V AC
110 V DC ... 250 V DC
Input voltage range
100 V AC ... 240 V AC ±10 %
110 V DC ... 250 V DC ±10 %
Nominal output current (IN)
Dynamic Boost (IDyn.Boost)
Typical national grid voltage
Voltage type of supply voltage
Inrush current integral (I<sup>2</sup>t)
Inrush current limitation
Frequency range (f<sub>N</sub>)
Mains buffering time
> 15 ms
> 15 ms (120 V AC)
> 15 ms (230 V AC)
Current consumption
1.1 A (250 V DC)
1.2 A (240 V AC)
2.4 A (110 V DC)
2.8 A (100 V AC)
Nominal power consumption
Protective circuit
Transient surge protection; Varistor
Input fuse
6.3 A (internal (device protection))
Recommended breaker for input protection
6 A ... 16 A (US/CAN: branch circuit protection 20 A) (Characteristic B, C, D, K or comparable)
Efficiency
typ. 91 % (120 V AC)
typ. 92 % (230 V AC)
Nominal output current (I<sub>N</sub>)
Dynamic Boost (I<sub>Dyn.Boost</sub>)
Derating
> 60 °C ... 70 °C (2.5 %/K)
Feedback voltage resistance
Protection against overvoltage at the output (OVP)
Control deviation
< 0.1 % (change in input voltage ±10 %)
< 1 % (change in load, static 10 % ... 90 %)
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
Maximum no-load power dissipation
< 10 W (120 V AC)
< 6 W (230 V AC)
Power loss nominal load max.
< 17 W (230 V AC)
< 22 W (120 V AC)
Rise time
≤ 12 ms (U<sub>OUT</sub> (10 % ... 90 %))
Connection in parallel
yes, for redundancy and increased capacity
Fuse protection (secondary side)
Maximum switching voltage
Connection method
IPD panel feed-through with Push-in spring connection
M12 circular connector
Conductor cross-section, rigid min.