EEM-MA770-24DC Measuring device
N
0%
1127052

EEM-MA770-24DC Measuring device

Manufactured by
Brand PHOENIX CONTACT
Multi-functional energy measuring device with 24 V DC supply and integrated Modbus/TCP interface for measuring electrical parameters in low-voltage installations up to 690 V (phoenixcontact.com/empro-help)
4063151055226
only
available
100+
51
pcs.
(2026-08-29)
Supply from Phoenix Contact’s warehouse
Product recommended retail price (RRP) is
000
46680 0 € pcs.
All prices without tax
All prices with tax
inquiry
only
available
100+
inquiry
0
2026-08-29
pcs.
Properties
Description
Dimensions
Files
Codes
Product type
Energy measuring device
Product family
EMpro
Number (Ethernet ports)
1
Display type
LCD display, backlit, 2-color, multi-line
Maximum power dissipation for nominal condition
10 VA
Mains type
3-phase (3 or 4-conductor), 2-phase (2-conductor), and single-phase (1-conductor)
Test voltage
4 kV AC (50 Hz, 60 s)
Pollution degree
2
Insulation
Functional insulation
Reinforced insulation
Standards/regulations
IEC 61010-1
IEC 61010-2-030
IEC 61326-1
IEC 61557-12
Overvoltage category
II (600 V AC)
III (300 V AC)
Measuring category
II (600 V AC)
III (300 V AC)
Supply voltage
24 V DC ±25 %
Supply voltage range
18 V DC ... 30 V DC
Power consumption
< 0.5 VA
< 4 W
Measuring principle
True r.m.s. value measurement (seamless)
Frequency measuring range (Fundamental component)
45 Hz ... 65 Hz
Measured value
AC sine (50 Hz/60 Hz)
Scanning rate
12,8 kHz (50 Hz) / 15,4 kHz (60 Hz)
Number of periods
10 (true RMS value at 50 Hz)
12 (true RMS value at 60 Hz)
Acquisition of harmonics
up to 63rd harmonic
Input name
Current measurement I1, I2, I3
Voltage measuring input V1, V2, V3
Input voltage range direct
11 V AC ... 400 V AC (Phase/neutral conductor)
18 V AC ... 690 V AC (Phase/Phase)
Input voltage range via external transformers
60 V AC ... 2000000 V AC (primary)
60 V AC ... 400 V AC (secondary)
Surge voltage capacity
760 V AC (Phase/Phase)
Precision
0.2 %
0.5 %
Input current
1 A (secondary)
5 A (secondary)
Measuring range
1 A ... 20000 A (primary)
Overload capacity
6 A (I<sub>max</sub>)
Response threshold from measuring range nominal value
10 mA (1 A)
50 mA (5 A)
Current overload
20 A (4 x I<sub>N</sub>,<sub> </sub>continuous)
50 A for 1 s
Active energy (IEC 62053-22)
Class 0.5 S
Reactive power (IEC 62053-23)
Class 2
ANSI C12.20
Class 0.5 S
Description of the input
Digital input in accordance with IEC/EN 61131-2 (type 3)
Number
1
Voltage input signal
0 V DC ... 30 V DC
24 V DC
Current input signal
2 mA ... 15 mA
Protection
250 mA (fast-blow)
Protective circuit
Protection against incorrect DC connection (max. 30 V)
Output description
Digital output in accordance with IEC/EN 61131-2 (type 3)
Current output signal
≤ 100 mA
Voltage output signal
24 V DC
Connection method
RJ45
Screw connection
Stripping length
7 mm
8 mm
Screw thread
M3
Conductor cross-section rigid
0.14 mm² ... 2.5 mm²
0.2 mm² ... 6 mm²
Conductor cross-section flexible
0.14 mm² ... 1.5 mm²
0.2 mm² ... 4 mm²
Conductor cross-section AWG
24 ... 10
26 ... 14
Tightening torque
0.5 Nm ... 0.6 Nm
Length
0
m
Width
0
m
Height
0
m
Weight Net
0
kg
Weight
0
kg
Package
0
kg
Volume
0
No files found
ECLASS-13.0
27142330
ECLASS-15.0
27142330
ETIM 10.0
EC002301
UNSPSC 21.0
41113600
GTIN
4063151055226
Item accessories
0%
EEM-MKT-DRA DIN rail adapter
N
2902078 EEM-MKT-DRA DIN rail adapter
7320 0 €
only
available
100+
inquiry
30
pcs.
No related items found