Notes on operation
The PLC-ATP partition plate must be installed for voltages greater than 250 V (L1, L2, L3) between identical terminal blocks on adjacent modules.
The PLC-ATP separating plate should be installed for safe isolation between adjacent modules
The system installer must ensure the touch protection of the product (at voltages > 25 V AC/60 V DC). The product is a built-in device without protection against direct contact.
Assembly note
in rows with zero spacing
The PLC-ATP separating plate is required at the start and end of every PLC terminal strip.
Typical input current at UN
10 mA (60 Hz)
8.5 mA (50 Hz)
Application
Filter to prevent interference
Mechanical service life
approx. 3x 10<sup>7</sup> cycles
Date of last data management
Maximum power dissipation for nominal condition
Test voltage (Winding/contact)
4 kV<sub>rms</sub> (50 Hz, 1 min., winding/contact)
Rated surge voltage
4 kV (Safe isolation, reinforced insulation, and 6 kV between input circuit and output contact current paths)
Nominal input voltage U<sub>N</sub>
Input voltage range
171.6 V DC ... 253 V DC (20 °C)
179.4 V AC ... 264.5 V AC (20 °C)
Nominal voltage (plugged-in electromechanical relay)
Typical input current at U<sub>N</sub>
10 mA (60 Hz)
8.5 mA (50 Hz)
Protective circuit
Bridge rectifier
RC element
Maximum switching voltage
Minimum switching voltage
Limiting continuous current
10 A (value applies to connections 12. If connections 12 are bridged, the normal value applies.)
6 A
Maximum inrush current
30 A (300 ms, N/O contact)
Interrupting rating (ohmic load) max.
144 W (24 V DC)
1500 VA (250 V AC)
240 W (24 V DC, value is valid for connections 12. If connections 12 are bridged, the normal value applies.)
2500 W (250 V AC, value is valid for connections 12. If connections 12 are bridged, the normal value applies.)
48 W (60 V DC)
50 W (110 V DC)
58 W (48 V DC)
80 W (220 V DC)
Switching capacity
0.2 A (DC13, 250 V)
2 A (DC13, 24 V)
6 A (AC15, 24 V)
6 A (AC15, 250 V)
Conductor cross-section rigid
Conductor cross-section flexible
0.14 mm² ... 2.5 mm²
0.2 mm² ... 2.5 mm² (Single ferrule)
2x 0.5 mm² ... 1 mm² (TWIN ferrule)
Conductor cross-section AWG
Degree of protection (Relay base)
Degree of protection (Relay)