Your Language:
English (en)
en
English
lt
Lietuviškai
Debug
Administrator
Testing
did you mean:
Show more results in separate page
0 items
000
Your basket is empty
Total price for 0 items 000
All prices without tax
All prices with tax
Order
Proceed to basket details
EEM-SB370-C
N
0%
1158951

EEM-SB370-C

Manufactured by
Brand PHOENIX CONTACT
Multi-functional energy measuring device without display, with integrated Ethernet and Proficloud.io interface for measuring electrical parameters in low-voltage installations up to 690 V. (phoenixcontact.com/empro-help)
4063151166410
No suppliers found
Product recommended retail price (RRP) is
000
94990 0 € pcs.
All prices without tax
All prices with tax
inquiry
only
available
100+
inquiry
0
pcs.
Properties
Description
Dimensions
Files
Codes
Product type
Energy measuring device
Product family
EMpro
Number (Ethernet ports)
3
Display type
none
IoT platform
PROFICLOUD
Supports cloud computing
yes
Protocol / IP-Port
HTTPS / 443
MQTT / 8883
Smart Services
Device Management Service
EMMA Service
Time Series Data Service
Maximum power dissipation for nominal condition
10 VA
Mains type
3-phase (3 or 4-conductor), 2-phase (2-conductor), and single-phase (1-conductor)
Test voltage
4 kV AC (50 Hz, 60 s)
Pollution degree
2
Insulation
Functional insulation
Reinforced insulation
Standards/regulations
IEC 61010-1
IEC 61010-2-030
IEC 61326-1
IEC 61557-12
Overvoltage category
II (600 V AC)
III (300 V AC)
Measuring category
II (600 V AC)
III (300 V AC)
Supply voltage range
100 V AC ... 230 V AC (±20 %)
150 V DC ... 250 V DC (±20 %)
Power consumption
< 0.5 VA
≤ 4 W
Nominal frequency
50 Hz ... 60 Hz (AC sine)
Measuring principle
True r.m.s. value measurement (seamless)
Frequency measuring range (Fundamental component)
45 Hz ... 65 Hz
Measured value
AC sine (50 Hz/60 Hz)
Scanning rate
12,8 kHz (50 Hz) / 15,4 kHz (60 Hz)
Number of periods
10 (true RMS value at 50 Hz)
12 (true RMS value at 60 Hz)
Acquisition of harmonics
up to 63rd harmonic
Input name
Current measurement I1, I2, I3
Voltage measuring input V1, V2, V3
Input voltage range direct
11 V AC ... 400 V AC (Phase/neutral conductor)
18 V AC ... 690 V AC (Phase/Phase)
Input voltage range via external transformers
60 V AC ... 2000000 V AC (primary)
60 V AC ... 400 V AC (secondary)
Surge voltage capacity
760 V AC (Phase/Phase)
Precision
0.2 %
0.5 %
Input current
1 A (secondary)
5 A (secondary)
Measuring range
1 A ... 20000 A (primary)
Overload capacity
6 A (I<sub>max</sub>)
Response threshold from measuring range nominal value
10 mA (1 A)
50 mA (5 A)
Current overload
20 A (4 x I<sub>N</sub>,<sub> </sub>continuous)
50 A for 1 s
Active energy (IEC 62053-22)
Class 0.5 S
Reactive power (IEC 62053-23)
Class 2
ANSI C12.20
Class 0.5 S
Description of the input
Digital input in accordance with IEC/EN 61131-2 (type 3)
Number
1
Voltage input signal
0 V DC ... 30 V DC
24 V DC
Current input signal
2 mA ... 15 mA
Protection
250 mA (fast-blow)
Protective circuit
Protection against incorrect DC connection (max. 30 V)
Output description
Digital output in accordance with IEC/EN 61131-2 (type 3)
Current output signal
≤ 100 mA
Voltage output signal
24 V DC
Connection method
RJ45
Screw connection
Stripping length
7 mm
8 mm
Screw thread
M3
Length
0
m
Width
0
m
Height
0
m
Weight Net
0
kg
Weight
0
kg
Package
0
kg
Volume
0
No files found
ECLASS-13.0
27142330
ECLASS-15.0
27142330
ETIM 10.0
EC002301
UNSPSC 21.0
41113600
GTIN
4063151166410