Supply system configuration
Star network (TN, TT, IT (PE))
Nominal input voltage range
Input voltage range
2x 400 V AC ... 500 V AC ±10 %
3x 400 V AC ... 500 V AC -20 % ... +10 %
Typical national grid voltage
Voltage type of supply voltage
Inrush current integral (I2t)
Mains buffering time
typ. 21 ms (3x 400 V AC)
typ. 21 ms (3x 480 V AC)
Current consumption
2x 2.1 A (2x 500 V AC)
2x 2.6 A (2x 400 V AC)
3x 1.2 A (3x 500 V AC)
3x 1.5 A (3x 400 V AC)
Protective circuit
Transient protection; Varistor
Device mains fuse
6.3 A internal (device protection)
Recommended breaker for input protection
3x 6 A ... 16 A (Characteristic B, C, D, K or comparable)
Efficiency
typ. 95.4 % (3x 400 V AC)
typ. 95.8 % (3x 480 V AC)
Setting range of the output voltage (USet)
Nominal output current (IN)
Dynamic Boost (IDyn.Boost)
Crest factor
typ. 1,53 (3x 480 V AC)
typ. 1.54 (3x 400 V AC)
Output power (PDyn. Boost)
Connection in parallel
yes, for increasing power and redundancy with diode
Connection in series
yes, for increased output voltage (observe SELV limit)
Feedback voltage resistance
Protection against overvoltage at the output (OVP)
Residual ripple
typ. 13 mV<sub>PP</sub> (with nominal values)
Control deviation
< 0.1 % (change in input voltage ±10 %)
< 1 % (change in load, static 10 % ... 90 %)
< 3 % (change in load, dynamic 10 % ... 90 %)
Rise time
≤ 1 s (U<sub>Out</sub> = 10 % ... 90 %)
Minimum no-load power dissipation
Maximum no-load power dissipation
Minimum nominal load power dissipation
Power loss nominal load max.
Integrated fuse protection
Fuse protection (secondary side)
Position marking
1.1 (L1), 1.2 (L2), 1.3 (L3), 1.4 ()
2.1, 2.2 (+), 2.3, 2.4, 2.5 (-)
3.1 (13), 3.2 (14)
rigid
0.2 mm² ... 1.5 mm²
0.2 mm² ... 4 mm²
0.5 mm² (recommended)
0.75 mm² ... 16 mm²
1.5 mm² (recommended)
10 mm² (recommended)
flexible
0.2 mm² ... 1.5 mm²
0.2 mm² ... 2.5 mm²
0.5 mm² (recommended)
0.75 mm² ... 16 mm²
1.5 mm² (recommended)
10 mm² (recommended)
flexible with ferrule without plastic sleeve
0.25 mm² ... 1.5 mm² (Cu)
0.25 mm² ... 2.5 mm²
0.5 mm² (recommended)
0.75 mm² ... 16 mm² (Cu)
1.5 mm² (recommended)
10 mm² (recommended)
flexible with ferrule with plastic sleeve
0.25 mm² ... 0.75 mm²
0.25 mm² ... 2.5 mm²
0.5 mm² (recommended)
0.75 mm² ... 10 mm²
1.5 mm² (recommended)
10 mm² (recommended)
AWG
16 (recommended)
20 ... 4 (Cu)
20 (recommended)
24 ... 12 (Cu)
24 ... 16 (Cu)
8 (recommended)
Stripping length
10 mm (Rigid/flexible/ferrule)
18 mm (Rigid/flexible/ferrule)
Types of signaling
LED DC OK - signal state operation (U<sub>N</sub> = 24 V DC, I<sub>Out</sub> = I<sub>N</sub>)
Function
Operating state forwarding
Visual operating state display
Color
red, yellow, green (multicolor LED)