Note on dimensions
The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715).
Supported protocols
BootP
DCP
DHCP
DLR
EtherNet/IP™
FTP
HTTP
SNMP
TFTP
Connection method
Bus base module
Push-in connection
RJ45 jack
USB type C
Note on the connection method
Auto negotiation and autocrossing
Please observe the information provided on conductor cross-sections in the “Axioline F: system and installation” user manual.
Transmission speed
10/100 Mbps (Half or full duplex mode (automatic detection, can be adjusted manually))
100 Mbps
Transmission physics
Ethernet in RJ45 twisted pair
Amount of process data (Input data)
Amount of process data (Output data)
Number of supported devices
Number of local bus devices that can be connected
Mounting position
any (observe temperature derating)
Special properties
Extreme conditions version
Overvoltage category
II (IEC 60664-1, EN 60664-1)
Pollution degree
2 (IEC 60664-1, EN 60664-1)
Maximum power dissipation for nominal condition
Supply voltage
24 V DC
5 V DC (via bus base module)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw
max. 670 mA (2.5 A on U<sub>Bus</sub>, U<sub>L</sub> = 24 V)
Protective circuit
Reverse polarity protection; electronic
Surge protection; electronic
Power supply unit
max. 2 A (Applications with UL approval, use in zone 2 potentially explosive area)
max. 2.5 A
Test voltage: Ethernet interface 1 / Ethernet interface 2
Test voltage: Ethernet interface 1 / 24 V communications voltage (UL) feed-in
Test voltage: Ethernet interface 2 / 24 V communications voltage (UL) feed-in
Test voltage: Ethernet interface 1 / functional ground
Test voltage: Ethernet interface 2 / functional ground
Test voltage: 24 V communications voltage (UL) feed-in / functional ground
Conductor cross-section, rigid
Conductor cross-section, flexible
Conductor cross-section AWG
Ambient temperature (operation)
-25 °C ... 55 °C (Standard, applications with UL approval, use in zone 2 potentially explosive area; mounting position: any)
-40 °C ... 70 °C (Extended, see section “Tested successfully: use under extreme ambient conditions” in the data sheet.)
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)
Permissible humidity (operation)
5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)
5 % ... 95 % (non-condensing)