Supply system configuration
Star network (TN, TT, IT (PE))
Input voltage range
100 V AC ... 240 V AC -15 % ... +10 %
110 V DC ... 250 V DC -20 % ... +10 %
Typical national grid voltage
Voltage type of supply voltage
Inrush current integral (I2t)
Mains buffering time
typ. 20 ms (120 V AC)
typ. 90 ms (230 V AC)
Current consumption
0.13 A (250 V DC)
0.31 A (110 V DC)
0.32 A (240 V AC)
0.59 A (100 V AC)
Protective circuit
Transient surge protection; Varistor
Device mains fuse
1.25 A internal (device protection), slow-blow
Recommended breaker for input protection
6 A ... 16 A (Characteristics B, C, D, K)
Efficiency
> 87 % (120 V AC)
> 88 % (230 V AC)
Nominal output current (IN)
Derating
> 50 °C ... 70 °C (2 % / K)
Connection in parallel
yes, for increasing power and redundancy with diode
Feedback voltage resistance
Protection against overvoltage at the output (OVP)
Control deviation
< 0.1 % (change in input voltage ±10 %)
< 1 % (Static load change 10 % ... 90 %)
< 4 % (Dynamic load change 10 % ... 90 %, (10 Hz))
Rise time
typ. 100 ms (U<sub>Out</sub> = 10 % ... 90 %)
Minimum no-load power dissipation
Maximum no-load power dissipation
Minimum nominal load power dissipation
Power loss nominal load max.
Integrated fuse protection
Fuse protection (secondary side)
Position marking
1.1, 1.2 (L), 1.3, 1.4 (N)
2.1, 2.2 (+), 2.3, 2.4 (-)
rigid
0.2 mm² ... 2.5 mm²
1 mm² (recommended)
flexible
0.2 mm² ... 2.5 mm²
1 mm² (recommended)
flexible with ferrule without plastic sleeve
0.5 mm² ... 1.5 mm²
1 mm² (recommended)
flexible with ferrule with plastic sleeve
0.2 mm² ... 1 mm²
1 mm² (recommended)
Stripping length
10 mm
10 mm (Ferrule)
10 mm (rigid/flexible)
Signal threshold
< 0.9 x U<sub>N </sub>(U<sub>N</sub> = 12 V DC) (LED off)
> 0.9 x U<sub>N </sub>(U<sub>N</sub> = 12 V DC) (LED lights up green)
Insulation voltage input/output
3.75 kV AC (routine test)
4 kV AC (type test)