Product type
Current measuring transducer
Insulation
Safe isolation in accordance with IEC/EN 61010-1
Step response (10-90%)
20 ms (DC)
200 ms (AC/DC)
Maximum temperature coefficient
Maximum transmission error
0.5 % (of nominal range value under nominal conditions)
Standards/regulations
EN 61000-6-4
IEC 61010-1
IEC 61010-2-030
Test voltage
2 kV AC (50 Hz, 60 s)
4 kV AC (50 Hz, 60 s)
Nominal supply voltage range
12 V DC ... 24 V DC -20 % ... +25 %
Input current range
-100 A DC ... 100 A DC
0 A AC ... 100 A AC
Measuring range
0 A AC/DC ... 100 A AC/DC
0 A AC/DC ... 50 A AC/DC
Setting range for min. input current
0 A AC/DC ... 18.8 A AC/DC
0 A AC/DC ... 9.4 A AC/DC
Setting range for max. input current
-125 A DC ... 125 A DC (DIN/EN 61010-1)
0 A AC/DC ... 125 A AC/DC (DIN/EN 61010-1)
0 A AC/DC ... 62.5 A AC/DC (DIN/EN 61010-1)
Overload capacity
2 x I<sub>N</sub> (continuous), depending on the fed-through conductor
Surge strength
20 x I<sub>N</sub> (1 s), depending on the fed-through conductor
Frequency measuring range
0 Hz ... 100 Hz
0 Hz ... 1000 Hz
0 Hz ... 200 Hz
0 Hz ... 500 Hz
Curve type
AC, DC or distorted currents
Connection method
Push-in connection
RS-485
Conductor cross-section rigid
0.2 mm² ... 2.5 mm²
25 mm²
Conductor cross-section flexible
Conductor cross-section AWG
Designation
Modbus/RTU interface configuration
WBM: Default address, USB-C interface
Note
Register contents, see register table
Address setting
Modbus default address: 1
Depth (Device depth (DIN rail mounting))
114.5 mm (Snapped onto DIN rail NS 35/7,5 in accordance with EN 60715)
Flammability rating according to UL 94
Ambient temperature (operation)
-40 °C ... 60 °C
-40 °F ... 140 °F
Ambient temperature (storage/transport)
Permissible humidity (operation)