Maximum continuous operating voltage UC
Type
DIN rail module, two-section, divisible
Protective conductor current IPE
Surge protection fault message
Optical, remote indicator contact
Standby power consumption PC
≤ 2.7 mVA (at U<sub>REF</sub>)
≤ 4.8 mVA (at U<sub>C</sub>)
Reference test voltage UREF
Nominal discharge current In (8/20) µs
Voltage protection level Up (L-N)
Connection name
Remote fault indicator contact
Voltage protection level Up (L-PE)
Voltage protection level Up (N-PE)
Operating voltage
125 V DC (200 mA DC)
250 V AC
TOV behavior at UT (L-N)
50 V AC (120 min / withstand mode)
Operating current
0.5 A AC
0.5 A DC (75 V DC)
TOV behavior at UT (L-PE)
50 V AC (120 min / withstand mode)
Conductor cross-section flexible
Short-circuit current rating ISCCR
3 kA DC (for 16 A gG / B backup fuse)
6 kA AC
Conductor cross-section rigid
Residual voltage Ures (L-N)
≤ 0.16 kV (at 0.5 kA)
≤ 0.2 kV (at 1 kA)
Conductor cross-section AWG
Residual voltage Ures (L-PE)
≤ 0.35 kV (at 0.5 kA)
≤ 0.4 kV (at 1 kA)
Residual voltage Ures (N-PE)
≤ 0.35 kV (at 0.5 kA)
≤ 0.4 kV (at 1 kA)
Depth
71.3 mm (incl. DIN rail 7.5 mm)
Color
light gray (RAL 7035)
traffic gray B (RAL 7043)
Flammability rating according to UL 94
Insulating material
PA 6.6-FR
PA 6.6-FR 20 % GF
Housing material
PA 6.6-FR
PA 6.6-FR 20 % GF