Rated insulation voltage Ui
Rated operating voltage Ue
125 V
24 V
240 V
250 V
440 V
60 V
Product family
Modular emergency stop switches
Rated operating current Ie
0.12 A
0.2 A
0.4 A
1 A
1.6 A
2 A
3 A
Application
Assembly with just 4 contact modules
Safe shutdown
Thermal continuous current Ith
Short-circuit current
1000 A (conditional short-circuit current I<sub>q</sub>)
Contact switching type
1 force-guided N/C contact
Positive opening action
in accordance with EN 60947-5-1, Annex K
Voltage
max. (see load limit current)
min. 5 V
Current
max. (see load limit current)
min. 1 mA
Electrical service life
10<sup>6</sup> switching cycles
Rated insulation voltage U<sub>i</sub>
Rated operating voltage U<sub>e</sub>
125 V
24 V
240 V
250 V
440 V
60 V
Rated operating current I<sub>e</sub>
0.12 A
0.2 A
0.4 A
1 A
1.6 A
2 A
3 A
Switching capacity
1.1x I<sub>e</sub>
10x I<sub>e</sub>
Thermal continuous current I<sub>th</sub>
Note regarding the connection technology
2 conductors possible per terminal point, with one conductor on each side of the screw
Conductor cross-section rigid
Conductor cross-section flexible
Flexible conductor cross-section with ferrule
Conductor cross-section AWG
20 ... 14 (rigid and flexible conductors without ferrules)
23 ... 14 (flexible conductors with ferrules)
Flammability rating according to UL 94
Ambient temperature (operation)
-30 °C ... 85 °C (in conjunction with lighting module max. 65°C)
Ambient temperature (storage/transport)
Maximum altitude
max. 2000 m (Above sea level)
Shock
15g / 11 ms, in accordance with IEC 60068-2-27