Rated control circuit supply voltage US
Rated control supply current IS
typ. 77 mA (at U<sub>S</sub>)
Mechanical service life
10x 10<sup>6</sup> cycles
approx. 10<sup>7</sup> cycles
Relay type
Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3
Typical response time
typ. 40 ms (For U<sub>s </sub>autostart)
Maximum power dissipation for nominal condition
17 W (U<sub>S</sub> = 26.4 V, I<sub>L</sub>² = 72 A², P<sub>Total max</sub> = 2.6 W + 14.4 W)
Rated surge voltage/insulation
See data sheet, section “Insulation coordination”.
Rated control circuit supply voltage U<sub>S</sub>
Rated control supply current I<sub>S</sub>
typ. 77 mA (at U<sub>S</sub>)
Power consumption at U<sub>S</sub>
Inrush current
< 2.5 A (typ. with U<sub>S</sub>, Δt = 1 ms)
max. 1 A
max. 6 A
min. 10 mA
Filter time
1 ms (Test pulse width of low test pulses)
1 s (Test pulse rate for low test pulse)
5 ms (in the event of voltage dips at U<sub>s</sub>)
No brightness test pulses / high test pulses permitted.
Protective circuit
Reverse polarity protection; Suppressor diode
Suppressor diode
Input voltage range "0" signal
Input voltage range "1" signal
Input current range "0" signal
Max. permissible overall conductor resistance
Output description
2 N/C contacts parallel, non-safety-related, floating
2 N/O contacts each in series, safety-related, floating
Diagnostic contact, 2 NC in series, floating
Contact switching type
2 N/C contacts in series
4 enabling current paths
Switching voltage
250 V AC/DC
max. 250 V AC/DC
min. 10 V AC/DC
Switching capacity
1 A (AC15)
1 A (DC13)
5 A (AC15)
6 A (DC13)
Limiting continuous current
1 A
6 A (Observe derating and load limit curve)
Sq. Total current
1 A<sup>2</sup>
72 A<sup>2</sup> (observe derating)
Output fuse
1 A (gL/gG)
1 A gL/gG
10 A gL/gG
4 A gL/gG (for low-demand applications)
Conductor cross-section rigid
Conductor cross-section flexible