Typ. starting time with Us
20 ms (when controlled via K1/K2)
Mechanical service life
10x 10<sup>6</sup> cycles
approx. 10<sup>7</sup> cycles
Relay type
Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3
Overvoltage category
II, III (See the section “Insulation coordination”)
Typ. starting time with U<sub>s</sub>
20 ms (when controlled via K1/K2)
Typical release time
20 ms (when requested via K1/K2)
Maximum power dissipation for nominal condition
16.4 W (U<sub>K1/K2</sub> = 26.4 V, I<sub>L</sub>² = 72 A², P<sub>Total max</sub> = 2 W + 14.4 W)
Rated surge voltage/insulation
See data sheet, section “Insulation coordination”.
Input voltage range "1" signal
Inrush current
max. 6 A
min. 10 mA
typ. 130 mA (Δt = 800 ms)
Max. permissible overall conductor resistance
Output description
2 N/O contacts each in series, safety-related, floating
Diagnostic contact, 2 NC in series, floating
Contact switching type
2 N/C contacts in series
4 enabling current paths
Switching voltage
max. 250 V AC/DC
min. 10 V AC/DC
Switching capacity
1 A (AC15)
1 A (DC13)
5 A (AC15)
6 A (DC13)
Limiting continuous current
1 A
6 A (Observe derating and load limit curve)
Sq. Total current
1 A<sup>2</sup>
72 A<sup>2</sup> (observe derating)
Output fuse
1 A gL/gG
10 A gL/gG
4 A gL/gG (for low-demand applications)
Conductor cross-section rigid
Conductor cross-section flexible
Conductor cross-section AWG
Operating voltage display
Color (Housing)
traffic gray B (RAL 7043)
Performance level (PL)
d (6 A DC13; 5 A AC15; 8760 switching cycles/year)
Safety Integrity Level (SIL)
2 (In conjunction with suitable evaluating device)