Typ. starting time with Us
< 25 ms (at Us / when controlled via A11/A12)
Mechanical service life
10x 10<sup>6</sup> cycles
approx. 10<sup>7</sup> cycles
Relay type
Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3
Typ. starting time with U<sub>s</sub>
< 25 ms (at Us / when controlled via A11/A12)
Typical release time
< 20 ms (at Us / when controlled via A11/A12)
Maximum power dissipation for nominal condition
16.7 W (U<sub>S</sub> = 26.4 V, I<sub>L</sub>² = 72 A², P<sub>Total max</sub> = 2.3 W + 14.4 W)
Rated surge voltage/insulation
See data sheet, section “Insulation coordination”.
Input voltage range "1" signal
Max. permissible overall conductor resistance
Output description
2 N/C contacts in series, floating
2 N/C contacts parallel, non-safety-related, floating
2 N/O contacts each in series, safety-related, floating
Contact switching type
1 confirmation current path
1 signaling current path
5 enabling current paths
Switching voltage
max. 250 V AC/DC
min. 10 V
min. 5 V AC/DC
Inrush current
max. 3 A
max. 6 A
min. 10 mA
Switching capacity
1.5 A (AC15)
3 A (AC15)
3 A (DC13)
5 A (DC13)
Limiting continuous current
3 A
6 A
6 A (observe derating)
Sq. Total current
36 A<sup>2</sup>
72 A<sup>2</sup> (observe derating)
9 A<sup>2</sup>
Output fuse
10 A gL/gG
3 A (gL/gG)
4 A gL/gG (for low-demand applications)
6 A (gL/gG)
Conductor cross-section rigid
Conductor cross-section flexible
Conductor cross-section AWG
Operating voltage display
Performance level (PL)
e (In conjunction with suitable evaluating device)