Note
2011
2012 + A11:2018
For pollution degree 3 and wiring with fork cable lugs, an additional minimum lateral distance of 1 mm to earthed conductive surfaces must be maintained for cross-sections ≥ 16 mm².<br/>No additional lateral distances are required for pollution degre
Nominal voltage UN
240 V AC ±10 % (TN)
240 V AC ±10 % (TT)
Maximum continuous operating voltage UC
Nominal discharge current In (8/20) µs
Maximum discharge current Imax (8/20) µs
Short-circuit current rating ISCCR
Type
DIN rail module, two-section, divisible
Voltage protection level Up
Residual voltage Ures
≤ 0.9 kV (at 3 kA)
≤ 1 kV (at 5 kA)
≤ 1.1 kV (at 10 kA)
≤ 1.35 kV (at I<sub>n</sub>)
Surge protection fault message
optical, remote signaling via optional module
TOV behavior at UT
350 V AC (5 s / withstand mode)
460 V AC (120 min / safe failure mode)
Nominal discharge current In
Maximum power dissipation for nominal condition
Nominal frequency f<sub>N</sub>
Connection method
Fork-type cable lug
Screw connection
Tightening torque
3 Nm ... 3.5 Nm
30 lb<sub>f</sub>-in.
Conductor cross-section flexible
1.5 mm² ... 25 mm²
1.5 mm² ... 35 mm² (without ferrule)
2x 1.5 mm² ... 16 mm² (2 conductors with the same cross-section)
Conductor cross-section rigid
1.5 mm² ... 50 mm²
2x 1.5 mm² ... 16 mm² (2 conductors with the same cross-section)
Conductor cross-section AWG
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve
Conductor cross-section, flexible, with ferrule, with plastic sleeve
1.5 mm² ... 35 mm²
2x 1.5 mm² ... 10 mm² (2 conductors with the same cross-section)
Conductor cross-section, flexible, with ferrule, without plastic sleeve
1.5 mm² ... 25 mm²
2x 1.5 mm² ... 16 mm² (2 conductors with the same cross-section)
Depth
71.5 mm (incl. DIN rail 7.5 mm)
Color
gray (RAL 7042)
light gray (RAL 7035)
Flammability rating according to UL 94
Nominal voltage U<sub>N</sub>
240 V AC ±10 % (TN)
240 V AC ±10 % (TT)
Maximum continuous operating voltage U<sub>C</sub>