Note
2011
2012 + A11:2018
For pollution degree 3, additional minimum lateral distances to grounded, conductive surfaces may need to be observed. See the table in the download area under the item Packing slip in the installation notes.<br/>For pollution degree 2, no additional
Nominal voltage UN
400/690 V AC ±10 % (TN-C)
Maximum continuous operating voltage UC
Standby power consumption PC
Nominal discharge current In (8/20) µs
Maximum discharge current Imax (8/20) µs
Type
DIN rail module, two-section, divisible
Total discharge current ITotal (8/20) µs
Short-circuit current rating ISCCR
Surge protection fault message
Optical, remote indicator contact
Voltage protection level Up
Residual voltage Ures
≤ 1.4 kV (at 3 kA)
≤ 1.6 kV (at 5 kA)
≤ 1.9 kV (at 10 kA)
≤ 2.1 kV (at I<sub>n</sub>)
TOV behavior at UT
581 V AC (5 s / withstand mode)
762 V AC (120 min / safe failure mode)
Nominal discharge current In
Nominal frequency f<sub>N</sub>
Connection name
Remote fault indicator contact
Max. required back-up fuse
AC operating voltage
5 V AC ... 150 V AC (≤ 5000 m (amsl))
5 V AC ... 250 V AC (≤ 2000 m (amsl) at pollution degree 2)
DC operating voltage
125 V DC (≤ 5000 m (amsl))
30 V DC
30 V DC (≤ 5000 m (amsl))
Insulation type
The product has double/reinforced insulation between the main and auxiliary circuit.
Connection method
Fork-type cable lug
Push-in connection
Screw connection
Tightening torque
3 Nm ... 3.5 Nm
30 lb<sub>f</sub>-in.
Conductor cross-section flexible
0.25 mm² ... 1.5 mm²
1.5 mm² ... 25 mm²
1.5 mm² ... 35 mm² (without ferrule)
2x 1.5 mm² ... 16 mm² (2 conductors with the same cross-section)
Conductor cross-section rigid
0.25 mm² ... 1.5 mm²
1.5 mm² ... 50 mm²
2x 1.5 mm² ... 16 mm² (2 conductors with the same cross-section)
Conductor cross-section AWG
14 ... 2
15 ... 2
24 ... 16
2 conductors with the same cross section, flexible, with TWIN ferrule with plastic sleeve
Conductor cross-section, flexible, with ferrule, with plastic sleeve
0.25 mm² ... 1.5 mm²
1.5 mm² ... 35 mm²
2x 1.5 mm² ... 10 mm² (2 conductors with the same cross-section)
Conductor cross-section, flexible, with ferrule, without plastic sleeve
0.25 mm² ... 0.75 mm²
1.5 mm² ... 25 mm²
2x 1.5 mm² ... 16 mm² (2 conductors with the same cross-section)
Depth
71.5 mm (incl. DIN rail 7.5 mm)