Inrush current integral (I2t)
Overvoltage category (EN 61558-2-16)
Supply system configuration
Input voltage range
100 V AC ... 240 V AC -15 % ... +10 %
100 V DC ... 250 V DC -10 % ... +10 %
Maximum altitude (Output power derating)
> 2000 m (Derating P<sub>OUT</sub>: 10 %/1000 m)
Nominal output current (IN)
640 mA (I<sub>BUS</sub> + I<sub>AUX</sub>)
Typical national grid voltage
Voltage type of supply voltage
Inrush current integral (I<sup>2</sup>t)
Frequency range (f<sub>N</sub>)
Mains buffering time
typ. 100 ms (100 V AC)
typ. 100 ms (230 V AC)
Current consumption
0.09 A (250 V DC)
0.22 A (100 V DC)
0.22 A (240 V AC)
0.41 A (100 V AC)
Protective circuit
Transient surge protection; Varistor
Device mains fuse
4 A internal (device protection), slow-blow
Recommended breaker for input protection
6 A ... 20 A (Characteristics B, C, D, K)
Efficiency
> 86 % (120 V AC)
> 86 % (230 V AC)
Nominal output current (I<sub>N</sub>)
640 mA (I<sub>BUS</sub> + I<sub>AUX</sub>)
Derating
> 45 °C ... 70 °C (2 % / K)
Output power (P<sub>N</sub>)
Connection in parallel
yes, 2
yes, for increased efficiency and redundancy
Feedback voltage resistance
Protection against overvoltage at the output (OVP)
Control deviation
< 0.1 % (change in input voltage ±10 %)
< 0.5 % (Static load change 10 % ... 90 %)
< 3 % (Dynamic load change 10 % ... 90 %, (10 Hz))
Rise time
typ. 100 ms
typ. 100 ms (U<sub>Out</sub> = 10 % ... 90 %)
Minimum no-load power dissipation
Maximum no-load power dissipation
Minimum nominal load power dissipation
Power loss nominal load max.
Integrated fuse protection
Position marking
1.1 (), 1.2 (N), 1.3 (L)
2.1 (BUS +), 2.2 (BUS -), 2.3 (AUX +), 2.4 (AUX -)
Connection method
Lever Push-in connection
Push-in connection
rigid
0.2 mm² ... 4 mm²
0.34 mm² ... 0.5 mm²
0.5 mm² (recommended)
1.5 mm² (recommended)
flexible
0.2 mm² ... 4 mm²
1.5 mm² (recommended)
flexible with ferrule without plastic sleeve
0.2 mm² ... 2.5 mm²
1.5 mm² (recommended)
flexible with ferrule with plastic sleeve
0.2 mm² ... 2.5 mm²
1.5 mm² (recommended)
rigid (AWG)
16 (recommended)
20 (recommended)
22 ... 20 (Cu)
24 ... 12 (Cu)
Stripping length
10 mm (Ferrule)
10 mm (solid)
5 mm ... 6 mm (solid)
Types of signaling
Display bar graph
Display DC OK BUS
Display temperature LED
LED DC OK AUX
Function
Visual operating state display