Typical input current at UN
15 mA (Relay ON)
4.3 mA (Relay OFF)
Mechanical service life
approx. 2x 10<sup>7</sup> cycles
Insulation
Safe isolation, reinforced insulation (partition plate PLC-ATP should be installed for safe isolation between adjacent modules).
Date of last data management
Maximum power dissipation for nominal condition
Nominal input voltage U<sub>N</sub>
Input voltage range
19.2 V DC ... 26.4 V DC (20 °C)
Nominal voltage (plugged-in electromechanical relay)
Typical input current at U<sub>N</sub>
15 mA (Relay ON)
4.3 mA (Relay OFF)
Typical release time
200 ms +130 ms (Typical interval time at U<sub>N</sub>)
Protective circuit
Surge protection; Freewheeling diode
Operating voltage display
Contact switching type
Single contact, 1 changeover contact
Maximum switching voltage
250 V AC/DC (Separating plate PLC-ATP must be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal blocks in adjacent modules.)
Minimum switching voltage
Limiting continuous current
Interrupting rating (ohmic load) max.
144 W (at 48 V DC)
240 W (at 24 V DC)
4000 W (for 250 V AC)
48 W (at 60 V DC)
50 W (at 110 V DC)
80 W (at 220 V DC)
Conductor cross-section rigid
Conductor cross-section flexible
0.14 mm² ... 2.5 mm²
0.2 mm² ... 2.5 mm² (Single ferrule)
2x 0.5 mm² ... 1.5 mm² (TWIN ferrule)
Conductor cross-section AWG
Tightening torque
0.45 Nm ... 0.55 Nm (Usually these terminal blocks must be supported during conductor connection (held by one hand, supported on the housing))
Flammability rating according to UL 94 (Housing)
Ambient temperature (operation)
Identification
EN 60068-2-60
ISA-S71.04. G3 Harsh Group
Assembly note
in rows with zero spacing