Nominal output current (IN)
Selective Fuse Breaking (ISFB)
60 A (0 °C ... 40 °C)
65 A (0 °C ... 40 °C)
Voltage type of supply voltage
Buffer period
10 min (10 A)
180 min (1 A)
Current consumption
1.7 A (charging process)
11.9 A (at nom. output current and charging)
17 A (maximum)
65 mA (No-load)
Efficiency
> 97.6 % (Mains operation, with charged energy storage)
96.41 %
Output voltage range
18 V DC ... 30 V DC
19.2 V DC ... 27.6 V DC (U<sub>OUT</sub> = U<sub>BAT</sub> - 0,5 V DC)
Nominal output current (I<sub>N</sub>)
Output current limit
> 15 A (Battery operation)
Derating
60 °C ... 70 °C (2.5 %/K)
Power dissipation
1.8 W (Mains operation)
3.1 W (Mains operation)
3.19 W (Mains operation)
4 W (Battery operation)
5.1 W (Battery operation)
6.3 W (Battery operation)
POWER BOOST (I<sub>Boost</sub>)
Selective Fuse Breaking (I<sub>SFB</sub>)
60 A (0 °C ... 40 °C)
65 A (0 °C ... 40 °C)
Duration
12 ms (SFB technology)
15 ms (SFB technology)
Nominal voltage U<sub>N</sub>
End-of-charge voltage
24 V DC ... 29 V DC (temperature compensated)
Battery module service life
6 Years ... 9 Years (20 °C)
Latest startup date (battery only)
6 Months (0 °C ... 20 °C)
Latest startup (battery only) - range
1 Months ... 3 Months (30 °C ... 40 °C)
3 Months ... 6 Months (20 °C ... 30 °C)
Accumulator type
2x BB Battery HR4.2-12FR (from UPS V/C-level 06)
Connection method
Push-in connection
Screw connection
Conductor cross-section, rigid min.
Conductor cross-section, rigid max.
Conductor cross-section flexible min.
Conductor cross-section flexible max.
Conductor cross-section AWG min.
Conductor cross-section AWG max.