Note on dimensions
The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715).
Transmission speed
500 kbps
max. 2 Mbps (Operating mode 2)
max. 500 kbps (Operating mode 1)
Connection method
D-SUB-9 female connector
Push-in connection
Amount of process data (INTERBUS input/output data max.)
Number of supported devices (INTERBUS)
max. 512 (in total, of which 255 are remote bus devices/bus segments)
Number of local bus devices that can be connected
max. 63 (observe current consumption)
Number of devices with parameter channel
Number of supported branch terminals with remote bus branch
Product family
PLCnext Control Extension
Diagnostics messages
Bus error in INTERBUS yes
Peripheral fault in INTERBUS yes
Maximum power dissipation for nominal condition
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw
max. 185 mA (with IBS OPTOSUB ... FO adapter)
typ. 110 mA (without IBS OPTOSUB ... FO adapter)
Protective circuit
Reverse polarity protection; Polarity protection diode
Transient protection; Suppressor diode
Conductor cross-section, rigid
Conductor cross-section, flexible
Conductor cross-section AWG
Ambient temperature (operation)
-25 °C ... 55 °C (2000 m ... 3000 m above mean sea level)
-25 °C ... 60 °C (up to 2000 m above sea level)
Permissible humidity (operation)
5 % ... 95 % (non-condensing)
Vibration resistance in accordance with EN 60068-2-6/IEC 60068-2-6
Shock in accordance with EN 60068-2-27/IEC 60068-2-27
Continuous shock in accordance with EN 60068-2-27/IEC 60068-2-27
Protection class
III (IEC 61140, EN 61140, VDE 0140-1)
Identification
ISA S71.04.2013 G3 Harsh Group A,<br/>DIN EN 60068-2-60:2016-06 Method 4
Possible mounting positions