Test voltage: PROFINET interface 1 / 24 V communications voltage (UL) feed-in
Test voltage: PROFINET interface 2 / 24 V communications voltage (UL) feed-in
Test voltage: 24 V communications voltage (UL) feed-in / functional ground
Note on dimensions
The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715).
EMC note
EMC: class A product, see manufacturer's declaration in the download area
Supported protocols
DCP
FTPS (firmware 2.00 or later)
HTTP (Firmware 1.xx)
HTTPS (firmware 2.00 or later)
LLDP
MRP
PROFINET
PTCP
SNMPv1
TFTP (Firmware 1.xx)
Connection method
Bus base module
Push-in connection
RJ45 jack
USB type C
Note on the connection method
Auto negotiation and autocrossing
Please observe the information provided on conductor cross-sections in the “Axioline F: system and installation” user manual.
Transmission speed
100 Mbps
100 Mbps (acc. to PROFINET standard)
Transmission physics
Ethernet in RJ45 twisted pair
Amount of process data (Input data)
Amount of process data (Output data)
Number of supported devices
Number of supported subslots
128 (Take the number of subslots per device into account for the calculation.)
Number of subslots per device (no IO-Link device in the Axioline F station)
2 (Bus coupler)
2 (other module, per slot)
Number of subslots per device (at least one IO-Link device in the Axioline F station)
1 (Bus coupler)
1 (other module, per slot)
10 (AXL F IOL8 2H, bus coupler with firmware version 1.xx)
10 (AXL SE IOL4, bus coupler with firmware version 1.xx)
5 (AXL SE IOL4, bus coupler with firmware version as of 2.00)
9 (AXL F IOL8 2H, bus coupler with firmware version as of 2.00)
Number of local bus devices that can be connected
Mounting position
any (observe temperature derating)
Overvoltage category
II (IEC 60664-1, EN 60664-1)
Pollution degree
2 (IEC 60664-1, EN 60664-1)
Maximum power dissipation for nominal condition
Supply voltage
24 V DC
5 V DC (via bus base module)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw
max. 600 mA (2.0 A on U<sub>Bus</sub>, U<sub>L</sub> = 24 V)
Current consumption
typ. 97 mA (without I/O modules, U<sub>L</sub> = 24 V)
Protective circuit
Reverse polarity protection; no
Surge protection; electronic
Test voltage: PROFINET interface 1 / PROFINET interface 2
Test voltage: PROFINET interface 1 / 24 V communications voltage (U<sub>L</sub>) feed-in
Test voltage: PROFINET interface 1 / functional ground
Test voltage: PROFINET interface 2 / 24 V communications voltage (U<sub>L</sub>) feed-in
Test voltage: PROFINET interface 2 / functional ground
Test voltage: 24 V communications voltage (U<sub>L</sub>) feed-in / functional ground