Test voltage: 5 V supply of the local bus (UBus) / 24 V supply (I/Os)
Test voltage: 5 V supply of the local bus (UBus) / functional ground
Note on dimensions
The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715).
Connection method
Bus base module
Push-in connection
Required configuration data
Protective circuit
Reverse polarity protection; parallel diode; with external 5 A fuse (only for commissioning)
Short-circuit protection, overload protection of the outputs; electronic
Surge protection; electronic (35 V, 0.5 s)
Limitation of the voltage induced on circuit interruption
Max. current carrying capacity per output
Maximum output current per module
8 A (provide external protection)
Output voltage when switched off
Output current when switched off
Nominal load, inductive
max. 12 VA (1.2 H, 48 Ω, with nominal voltage)
Nominal load, lamp
max. 12 W (at nominal voltage)
Nominal load, ohmic
max. 12 W (48 Ω, with nominal voltage)
Switching frequency
max. 1 per second (with inductive load)
max. 10000 per second (with at least 50 mA load current)
max. 16 per second (with nominal lamp load)
Reverse voltage resistance to short pulses
limited protection up to 0.5 A for 1 s
Behavior with overload
Shutdown with automatic restart
Behavior with inductive overload
Signal delay
max. 100 µs (when switched off, with at least 50 mA load current)
max. 100 µs (when switched on)
Output current with ground connection interrupt when switched off
Mounting position
any (no temperature derating)
Scope of supply
including bus base module and Axioline F connectors
Overvoltage category
II (IEC 60664-1, EN 60664-1)
Pollution degree
2 (IEC 60664-1, EN 60664-1)
Maximum power dissipation for nominal condition
Supply voltage
24 V DC
5 V DC (via bus base module)
Current draw
max. 120 mA (up to HW 02)
max. 60 mA (from HW 03)
max. 8 A (provide external protection)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current consumption
min. 14 mA (without actuators)