Test voltage: 5 V supply of the local bus (UBus) / 24 V supply (I/Os)
Test voltage: 5 V supply of the local bus (UBus) / functional ground
Note on dimensions
The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715).
Connection method
Bus base module
Push-in connection
Required configuration data
Description of the input
Inputs for thermocouples or linear voltage
Number of inputs
8 + 1 (8 inputs for thermocouples or linear voltage, plus 1 input -5 V to +5 V)
Connection technology
2-conductor (shielded, twisted pair)
Sensor types (RTD) that can be used
Pt 100 (4 external cold junctions, can also be used as a sensor input)
Sensor types that can be used (TC)
U, T, L, J, E, K, N, S, R, B, C, W, HK
Tolerance, relative
see tables for tolerance values
typ. 0.01 % (Thermocouple type K, NiCr-Ni)
Tolerance, absolute
see tables for tolerance values
typ. ± 0.19 K (Thermocouple type K, plus tolerance of cold junction)
Measured value representation
16 bits (15 bits + sign bit)
Input filter time
100 ms
120 ms (adjustable)
40 ms
60 ms
Protective circuit
Reverse polarity protection; Polarity protection diode
Surge protection; electronic (35 V, 0.5 s)
Transient protection of inputs
Transient protection; Suppressor diode
Mounting position
any (no temperature derating; Parameterize the mounting position using the object 0080<sub>hex</sub> ParaTable!)
Scope of supply
including bus base module and Axioline F connectors
Overvoltage category
II (IEC 60664-1, EN 60664-1)
Pollution degree
2 (IEC 60664-1, EN 60664-1)
Maximum power dissipation for nominal condition
Supply voltage
24 V DC
5 V DC (via bus base module)
Current draw
max. 180 mA
max. 70 mA
typ. 115 mA
typ. 45.3 mA
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Test voltage: 5 V supply of the local bus / 24 V supply (I/Os)
Test voltage: 5 V supply of the local bus (U<sub>Bus</sub>) / functional ground
Test voltage: 24 V supply (I/O) / functional ground
Note on the connection method
Please observe the information provided on conductor cross-sections in the “Axioline F: system and installation” user manual.
Conductor cross-section, rigid
Conductor cross-section, flexible
Conductor cross-section AWG
Ambient temperature (operation)