Test voltage: PROFIBUS interface / 24 V communications voltage (UL) feed-in
Test voltage: 24 V communications voltage (UL) feed-in / functional ground
Note on dimensions
The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715).
Connection method
Bus base module
D-SUB-9 female connector
Micro USB type B
Push-in connection
Transmission speed
100 Mbps
9.6 kbps ... 12 Mbps
Max. number of local bus devices
63 (Consider the logic current consumed by the devices)
Amount of process data (Input data)
Amount of process data (Output data)
Number of configuration data
Number of supported devices
Number of local bus devices that can be connected
Mounting position
any (observe temperature derating)
Overvoltage category
II (IEC 60664-1, EN 60664-1)
Pollution degree
2 (IEC 60664-1, EN 60664-1)
Maximum power dissipation for nominal condition
Supply voltage
24 V DC
5 V DC (via bus base module)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current draw
max. 567 mA (with 2 A at U<sub>Bus</sub> for the I/Os and U<sub>L</sub> = 24 V)
Current consumption
typ. 101 mA (without I/Os and U<sub>L</sub> = 24 V)
Protective circuit
Reverse polarity protection; electronic
Surge protection; electronic
Test voltage: PROFIBUS interface / 24 V communications voltage (U<sub>L</sub>) feed-in
Test voltage: PROFIBUS interface / functional ground
Test voltage: 24 V communications voltage (U<sub>L</sub>) feed-in / functional ground
Note on the connection method
Please observe the information provided on conductor cross-sections in the “Axioline F: system and installation” user manual.
Conductor cross-section, rigid
Conductor cross-section, flexible
Conductor cross-section AWG
Ambient temperature (operation)
-25 °C ... 55 °C (Mounting position: any)
-25 °C ... 60 °C (Mounting position: panel mounting on horizontal DIN rail)
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Ambient temperature (storage/transport)
Permissible humidity (operation)
5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)
5 % ... 95 % (non-condensing)
Vibration resistance in accordance with EN 60068-2-6/IEC 60068-2-6