Typ. starting time with Us
< 200 ms (when controlled via A1, automatic start)
Rated control circuit supply voltage US
20.4 V DC ... 26.4 V DC
24 V DC -15 % / +10 %
Rated control supply current IS
typ. 75 mA (depending on load M1 +100 mA)
Application
Ex
High demand
Low demand
Safe switch off
Relay type
Electromechanical relay with force-guided contacts in accordance with IEC/EN 61810-3
Typ. starting time with U<sub>s</sub>
< 200 ms (when controlled via A1, automatic start)
Typical release time
< 35 ms (when controlled via A1)
Maximum power dissipation for nominal condition
5.5 W (I<sub>L</sub>² = 60 A²)
Rated surge voltage/insulation
Rated control circuit supply voltage U<sub>S</sub>
20.4 V DC ... 26.4 V DC
24 V DC -15 % / +10 %
Rated control supply current I<sub>S</sub>
typ. 75 mA (depending on load M1 +100 mA)
Power consumption at U<sub>S</sub>
Inrush current
< 10 mA
max. 6 A
min. 3 mA
typ. 400 mA (Δt < 100 µs at U<sub>s</sub>)
Filter time
≥ 100 ms (at A1-A2; test pulse rate)
max. 2 ms (at A1-A2; test pulse width)
Max. permissible overall conductor resistance
Voltage at input/start and feedback circuit
Output description
2 NO contacts each in series, without delay, floating
PNP
Number of outputs
1 (non-safety-related)
2 (safety-related)
Switching voltage
max. 250 V AC/DC
min. 12 V AC/DC
Switching capacity
4 A (24 V (DC13))
5 A (250 V (AC15))
Limiting continuous current
4 A (Low demand)
6 A (High demand)
Sq. Total current
60 A<sup>2</sup> (observe derating)
Mechanical service life
10x 10<sup>6</sup> cycles
Output fuse
150 mA fast blow
4 A gL/gG (for low-demand applications)
6 A gL/gG
Voltage
approx. 22 V DC (U<sub>s</sub> - 2 V)
Maximum inrush current
500 mA (Δt = 1 ms at U<sub>s</sub>)
Conductor cross-section rigid
Conductor cross-section flexible