Test voltage: 7.5 V supply (bus logic), 24 V supply UANA / I/O
Connection method
Inline data jumper
Spring-cage connection
Required configuration data
Description of the input
Temperature sensor inputs
Sensor types (RTD) that can be used
Pt, Ni sensors, linear resistors
Sensor types that can be used (TC)
B, C, E, J, K, L, N, R, S, T, U, mV input
Tolerance, relative
see tables for tolerance values
Tolerance, absolute
see tables for tolerance values
typ. ± 0.3 K (Pt 100 with 3-wire connection)
Measured value representation
16 bits (15 bits + sign bit)
Process data update
100 ms (with filter time of 400 ms or 1600 ms)
20 ms (with filter time of 20 ms or 100 ms)
Scope of supply
including Inline connectors and marking fields
Operating mode
Process data mode with 10 words, PCP with 2 words
Overvoltage category
II (IEC 60664-1, EN 60664-1)
Pollution degree
2 (IEC 60664-1, EN 60664-1)
Maximum power dissipation for nominal condition
Supply voltage
24 V DC (via voltage jumper)
7.5 V DC (via voltage jumper)
Current draw
max. 100 mA
typ. 24 mA
typ. 90 mA
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Test voltage: 5 V supply, incoming remote bus/7.5 V supply (bus logics)
Test voltage: 5 V supply, outgoing remote bus/7.5 V supply (bus logics)
Test voltage: 7.5 V supply (bus logic), 24 V supply U<sub>ANA</sub> / I/O
Conductor cross-section, rigid
Conductor cross-section, flexible