Test voltage: 5 V supply of the local bus (UBus) / 24 V supply (I/Os)
Test voltage: 5 V supply of the local bus (UBus)/analog outputs
Test voltage: 5 V supply of the local bus (UBus) / functional ground
Note on dimensions
The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715).
Volume concentration H2S (Hydrogen sulfide)
Volume concentration NO2 (Nitrogen dioxide)
Volume concentration Cl2 (Chlorine)
Volume concentration SO2 (Sulfur dioxide)
Connection method
Bus base module
Push-in connection
Required configuration data
Note regarding the connection technology
Protective circuit
Reverse polarity protection; Polarity protection diode
Short-circuit and overload protection; Electronic
Surge protection; electronic (35 V, 0.5 s)
Transient protection; Suppressor diode
Representation of output values
Current output signal
0 mA ... 20 mA
4 mA ... 20 mA
Load/output load current output
Voltage output signal
-10 V ... 10 V
-5 V ... 5 V
0 V ... 10 V
0 V ... 5 V
Load/output load voltage output
Mounting position
any (no temperature derating)
Scope of supply
including bus base module and Axioline F connectors
Special properties
Extreme conditions version
Overvoltage category
II (IEC 60664-1, EN 60664-1)
Pollution degree
2 (IEC 60664-1, EN 60664-1)
Maximum power dissipation for nominal condition
Supply voltage
24 V DC
5 V DC (via bus base module)
Current draw
max. 110 mA (4 current channels, 20 mA output, 500 Ω load)
max. 125 mA (4 current channels, 24 mA output, 500 Ω load)
max. 150 mA
max. 85 mA (4 voltage channels, 10 V output)
typ. 120 mA
typ. 60 mA (4 voltage channels, 10 V output)
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Current consumption
min. 40 mA (Internal current consumption, 4 voltage channels, output 0 V, load > 10 MΩ)
Test voltage: 5 V supply of the local bus / 24 V supply (I/Os)
Test voltage: 5 V supply of the local bus (U<sub>Bus</sub>)/analog outputs
Test voltage: 5 V supply of the local bus (U<sub>Bus</sub>) / functional ground
Test voltage: 24 V supply (I/O)/analog outputs