CCCex note
Use in potentially explosive areas is not permitted in China.
MTTF
1923 Years (SN 29500 standard, temperature 40°C, operating cycle 34.25%)
3305 Years (SN 29500 standard, temperature 25°C, operating cycle 21%)
911 Years (SN 29500 standard, temperature 40°C, operating cycle 100%)
Maximum power dissipation for nominal condition
Test voltage data interface/power supply
1.5 kV AC (50 Hz, 1 min.)
Supply voltage range
18 V DC ... 30 V DC (via pluggable COMBICON screw terminal block)
Nominal supply voltage
24 V DC (via pluggable COMBICON screw terminal block)
Typical current consumption
10 mA (24 V DC, no load on D-SUB)
60 mA (24 V DC, current drain at D-SUB of 150 mA)
Max. current consumption
12 mA (18 V DC, no load on D-SUB)
77 mA (18 V DC, current drain at D-SUB of 150 mA)
Status and diagnostic indicators
LEDs: US (power supply), ACT (data activity)
Single conductor/terminal point, rigid
0.2 mm² ... 1.5 mm²
0.2 mm² ... 2.5 mm²
Single-wire/terminal point, flexible
0.2 mm² ... 1.5 mm²
0.2 mm² ... 2.5 mm²
Conductor cross-section, flexible [AWG]
Tightening torque
0.4 Nm (D-SUB interface)
0.6 Nm ... 0.8 Nm
Signal
± 1 kV (Data line, asymmetrical)
± 2.2 kV (Test Level 3)
Modbus
PROFIBUS
Serial transmission speed
Transmission length
≤ 1200 m (Depends on transmission speed and cable type)
Termination resistor
220 Ω
390 Ω
390 Ω (Can be connected)
Max. AWG conductor cross-section, flexible
Min. AWG conductor cross-section, flexible
Single-wire/terminal point, rigid AWG max.
Single-wire/terminal point, rigid AWG min.
Free fall in accordance with EN 60068-2-31
Vibration resistance in accordance with EN 60068-2-6/IEC 60068-2-6
Operation: 5g, 10...150 Hz, 2.5 h, in XYZ direction
Shock in accordance with EN 60068-2-27/IEC 60068-2-27
Operation: 25g, 11 ms period, half-sine shock pulse
Ambient temperature (operation)
Ambient temperature (storage/transport)
Altitude
≤ 2000 m (Restrictions for ATEX applications)
≤ 5000 m (For restrictions, see the manufacturer's declaration for altitude operation)
Permissible humidity (operation)
10 % ... 95 % (non-condensing)
Air pressure (operation)
≤ 80 kPa (When used in EX zone 2)
Certificate
CE-compliant
PxCIF16ATEX2702636X
Identification
508 Listed
ISA-S71.04-1985 G3 Harsh Group A
II 3 G Ex ec IIC T4 Gc
Note
Please follow the special installation instructions in the documentation!
Electromagnetic compatibility
Conformance with EMC Directive 2014/30/EU
Standards/regulations
EN 55011
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6