Measuring category
CAT III 300 V / CAT II 400 V in accordance with DIN EN 61010-1 and DIN EN 61010-2-030
Note on dimensions
The depth applies when a TH 35-7.5 DIN rail is used (in accordance with EN 60715).
Measuring range
0 A AC ... 6 A AC (overrange starting at 5 A)
0 V AC ... 440 V AC (Phase/neutral conductor)
0 V AC ... 760 V AC (Phase/Phase)
EMC note
EMC: class A product, see manufacturer's declaration in the download area
Overload
1.2 times the nominal value
1.4 times continuous; 150 A for 10 ms
Tolerance, relative
0.25 % (of the nominal value)
8k samples/s
Connection method
Bus base module
Push-in connection
Nominal voltage range
0 V AC ... 400 V AC (Phase/neutral conductor)
0 V AC ... 690 V AC (Phase/Phase)
Required configuration data
Input name
Current measuring input
Voltage measuring input
Test voltage: 5 V supply for local bus (UBus) / peripheral range AC
Test voltage: 5 V supply of the local bus (UBus) / functional ground
Mounting position
any (no temperature derating)
Operating mode
Process data mode with 32 words
Pollution degree
2 (IEC 60664-1, EN 60664-1)
Maximum power dissipation for nominal condition
Supply voltage
5 V DC (via bus base module)
Test voltage: 5 V supply for local bus (U<sub>Bus</sub>) / peripheral range AC
Test voltage: 5 V supply of the local bus (U<sub>Bus</sub>) / functional ground
Test voltage: Peripheral range for AC/functional ground
Note on the connection method
Conductor cross-section, rigid
Conductor cross-section, flexible
Conductor cross-section AWG