2011
2012
Max. single impulse: 100 kA (8/20 µs)
SPD according to AS/NZS 1768 Cat. C3
Maximum continuous operating voltage UC
Nominal discharge current In (8/20) µs
Maximum discharge current Imax (8/20) µs
Impulse discharge current (10/350) µs, peak value limp
Follow current interrupt rating Ifi
Type
DIN rail module, two-section, divisible
Short-circuit current rating ISCCR
Surge protection fault message
Optical, remote indicator contact
Voltage protection level Up
Residual voltage Ures
≤ 0.9 kV (at 2.5 kA)
≤ 1 kV (at 5 kA)
≤ 1.2 kV (at 12.5 kA)
≤ 1.5 kV (at I<sub>n</sub>)
≤ 2.5 kV (at 50 kA)
TOV behavior at UT
415 V AC (5 s / withstand mode)
460 V AC (120 min / withstand mode)
Nominal frequency f<sub>N</sub>
Connection name
Remote fault indicator contact
Operating voltage
12 V AC ... 250 V AC
125 V DC (200 mA DC)
Operating current
1 A DC (30 V DC)
10 mA AC ... 1 A AC
Connection method
Fork-type cable lug
Plug-in/screw connection via COMBICON
Screw connection
Conductor cross-section flexible
0.14 mm² ... 1.5 mm²
1.5 mm² ... 16 mm²
2.5 mm² ... 35 mm²
Conductor cross-section rigid
0.14 mm² ... 1.5 mm²
2.5 mm² ... 35 mm²
Conductor cross-section AWG
Depth
74.5 mm (incl. DIN rail 7.5 mm)
Flammability rating according to UL 94