Nominal voltage UN
240 V AC (230/400 V AC ... 240/415 V AC)
240/415 V AC (TN-S)
240/415 V AC (TT)
Maximum continuous operating voltage UC (L-N)
Maximum continuous operating voltage UC (L-PE)
Maximum continuous operating voltage UC (N-PE)
Type
Module for 60 mm system technology
Protective conductor current IPE
Nominal discharge current In (8/20) µs
Surge protection fault message
Optical, remote indicator contact
Maximum discharge current Imax (8/20) µs (L-N)
Maximum discharge current Imax (8/20) µs (L-PE)
Maximum discharge current Imax (8/20) µs (N-PE)
Follow current interrupt rating Ifi (N-PE)
Nominal frequency f<sub>N</sub>
Nominal voltage U<sub>N</sub>
240 V AC (230/400 V AC ... 240/415 V AC)
240/415 V AC (TN-S)
240/415 V AC (TT)
Short-circuit current rating ISCCR
Connection name
Remote fault indicator contact
Voltage protection level Up (L-N)
Voltage protection level Up (N-PE)
Operating voltage
125 V DC (200 mA DC)
5 V AC ... 250 V AC
Residual voltage Ures (L-N)
≤ 1.7 kV (at 3 kA)
≤ 1.8 kV (at 5 kA)
≤ 1.9 kV (at 10 kA)
≤ 2.1 kV (at I<sub>n</sub>)
Operating current
1 A DC (30 V DC)
5 mA AC ... 1 A AC
Residual voltage Ures (L-PE)
≤ 1.8 kV (at 3 kA)
≤ 1.9 kV (at 5 kA)
≤ 2 kV (at 10 kA)
≤ 2.3 kV (at I<sub>n</sub>)
Connection method
60 mm power rail system
Pluggable screw connection
Screw connection
Residual voltage Ures (N-PE)
≤ 0.5 kV (at 10 kA)
≤ 0.5 kV (at 3 kA)
≤ 0.5 kV (at 5 kA)
≤ 0.5 kV (at I<sub>n</sub>)
TOV behavior at UT (L-N)
415 V AC (5 s / withstand mode)
440 V AC (120 min / safe failure mode)
TOV behavior at UT (N-PE)
1200 V AC (200 ms / withstand mode)
Conductor cross-section flexible
0.14 mm² ... 1.5 mm²
2.5 mm² ... 16 mm²
Conductor cross-section rigid
0.14 mm² ... 1.5 mm²
2.5 mm² ... 25 mm²
Conductor cross-section AWG
Flammability rating according to UL 94