EMC note
EMC: class A product, see manufacturer's declaration in the download area
Electrical isolation between input and output
Linearity error
< 0.05 % (for full measuring range)
Maximum power dissipation for nominal condition
Maximum temperature coefficient
Transmission error in the set measuring range
((90 K / set measuring range [K]) + 0.05)%
Transmission error in the full measuring range
Standards/regulations
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6
EN 61000-6-4
IEC/EN 61010
Designation
Conducted interferences
Electromagnetic RF field
Fast transients (burst)
Loop-powered
Max. current consumption
< 4.5 mA (without signal current)
Power consumption
< 150 mW (without signal current)
Configurable/programmable
Sensor types (RTD) that can be used
Pt 100 (IEC 60751/EN 60751)
Temperature measuring range
Temperature measuring range: Pt 100
-150 °C ... 300 °C (configurable)
Max. permissible overall conductor resistance
Error detection limit (short-circuit)
Error detection limit (underrange)
30 Ω ≤ (start span - 2.5% span)
Error detection limit (overrange)
(end span + 2.5% span) ≤ approx. 254 Ω
Error detection limit (wire break)
Current output signal
20 mA ... 4 mA
4 mA ... 20 mA
Max. current output signal
Load/output load current output
(U<sub>supply </sub>- 12 V) / 22 mA
Ripple
< 20 mV<sub>PP</sub> (at 500 Ω)
Conductor cross-section rigid
Conductor cross-section flexible
Conductor cross-section AWG