CCCex note
Use in potentially explosive areas is not permitted in China.
Connection method
Inline data jumper
Spring-cage connection
Transmission speed
500 kbps / 2 Mbps (Can be used in Inline stations with these transmission speeds)
Required configuration data
Special properties
24 V DC
U<sub>M</sub>, U<sub>S</sub>
Protection class
III (IEC 61140, EN 61140, VDE 0140-1)
Overvoltage category
II (IEC 60664-1, EN 60664-1)
Pollution degree
2 (IEC 60664-1, EN 60664-1)
Maximum power dissipation for nominal condition
Test section
24 V supply (I/O) / functional ground 500 V AC 50 Hz 1 min
7.5 V supply (bus logic)/functional ground 500 V AC 50 Hz 1 min
7.5 V supply (bus logics)/24 V supply (I/O) 500 V AC 50 Hz 1 min
Protective circuit
Reverse polarity protection; Parallel polarity protection diode
Surge protection; Suppressor diode
Supply voltage
24 V DC (via Inline connector)
Supply voltage range
19.2 V ... 30 V (including all tolerances, including ripple)
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Power supply
max. 8 A (sum of U<sub>M </sub>+ U<sub>S</sub>)
Conductor cross-section, rigid
Conductor cross-section, flexible
Conductor cross-section AWG
Ambient temperature (operation)
Ambient temperature (storage/transport)
Permissible humidity (operation)
10 % ... 95 % (non-condensing)
Permissible humidity (storage/transport)
10 % ... 95 % (non-condensing)
Air pressure (operation)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Air pressure (storage/transport)
70 kPa ... 106 kPa (up to 3000 m above sea level)
Vibration resistance in accordance with EN 60068-2-6/IEC 60068-2-6
Shock in accordance with EN 60068-2-27/IEC 60068-2-27