Connection method
Inline data jumper
Spring-cage connection
Required configuration data
Description of the input
Input for resistive temperature sensors
Sensor types (RTD) that can be used
Pt, Ni, KTY, Cu sensors, linear resistors
Tolerance, relative
max. 0.25 % (Pt 100 with 3-wire connection)
see tables for tolerance values
typ. 0.06 % (Pt 100 with 3-wire connection)
Tolerance, absolute
see tables for tolerance values
typ. ± 0.5 K (Pt 100 with 3-wire connection)
Data formats
IB IL, IB ST, S7 compatible
Measured value representation
16 bits (15 bits + sign bit)
Linear resistance measuring range
0 Ω ... 20 kΩ
0 Ω ... 400 Ω
Process data update
6 ms (Up to 230 ms possible depending on operating mode)
Scope of supply
including Inline connectors and marking fields
Operating mode
Process data mode with 5 words/1 word PCP
Overvoltage category
II (IEC 60664-1, EN 60664-1)
Pollution degree
2 (IEC 60664-1, EN 60664-1)
Maximum power dissipation for nominal condition
Supply voltage
24 V DC (via voltage jumper)
7.5 V DC (via voltage jumper)
Current draw
max. 100 mA
max. 55 mA
typ. 28 mA
typ. 75 mA
Supply voltage range
19.2 V DC ... 30 V DC (including all tolerances, including ripple)
Test voltage: 7.5 V supply (bus logic)/±15.5 V, ±5 V analog supply (analog I/O)
Test voltage: 7.5 V supply (bus logic)/functional ground
Test voltage: ±15.5 V, ±5 V analog supply (analog I/O)/functional ground
Conductor cross-section, rigid
Conductor cross-section, flexible
Conductor cross-section AWG