Inrush current integral (I2t)
Nominal input voltage range
Input voltage range
85 V AC ... 264 V AC (derating < 90 V AC: 2.5 % per Kelvin)
Setting range of the output voltage (USet)
30 V DC ... 56 V DC (> 48 V DC, constant capacity restricted)
Derating
< 90 V AC (2.5 %/V)
55 °C ... 70 °C (2.5 %/K)
Nominal output current (IN)
Input voltage range AC
85 V AC ... 264 V AC (derating < 90 V AC: 2.5 % per Kelvin)
Voltage type of supply voltage
Inrush current integral (I<sup>2</sup>t)
Mains buffering time
> 13 ms (120 V AC)
> 18 ms (230 V AC)
Current consumption
2.4 A (230 V AC)
4.6 A (120 V AC)
Nominal power consumption
Protective circuit
Transient surge protection; Varistor
Recommended breaker for input protection
16 A (Characteristics B, C, D, K)
Efficiency
> 91 % (for 230 V AC and nominal values)
Setting range of the output voltage (U<sub>Set</sub>)
30 V DC ... 56 V DC (> 48 V DC, constant capacity restricted)
Nominal output current (I<sub>N</sub>)
Feedback voltage resistance
Protection against overvoltage at the output (OVP)
Active current limitation
Approx 11.4 A (in the event of a short-circuit)
Control deviation
< 0.1 % (change in input voltage ±10 %)
< 1 % (change in load, static 10 % ... 90 %)
< 2 % (change in load, dynamic 10 % ... 90 %)
Peak switching voltages nominal load
Maximum no-load power dissipation
Power loss nominal load max.
Rise time
< 2 ms (U<sub>OUT</sub> (10 % ... 90 %))
Connection in parallel
yes, for redundancy and increased capacity
Conductor cross-section, rigid min.
Conductor cross-section, rigid max.
Conductor cross-section flexible min.
Conductor cross-section flexible max.
Conductor cross-section AWG min.
Conductor cross-section AWG max.