Inrush current integral (I2t)
Nominal input voltage range
Input voltage range
85 V AC ... 264 V AC
90 V DC ... 350 V DC
Setting range of the output voltage (USet)
18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN)
3.5 A (-25 °C ... 60 °C, U<sub>OUT</sub> = 24 V DC)
POWER BOOST (IBoost)
4 A (-25 °C ... 40 °C permanent, U<sub>OUT</sub> = 24 V DC )
Selective Fuse Breaking (ISFB)
Voltage type of supply voltage
Inrush current integral (I<sup>2</sup>t)
Mains buffering time
typ. 20 ms (120 V AC)
typ. 80 ms (230 V AC)
Current consumption
0.4 A (220 V DC)
0.8 A (230 V AC)
0.9 A (110 V DC)
1.4 A (120 V AC)
Nominal power consumption
Protective circuit
Transient surge protection; Varistor
Input fuse
5 A (slow-blow, internal)
Permissible DC backup fuse
DC: Connect a suitable fuse upstream
Recommended breaker for input protection
6 A ... 20 A (AC: Characteristics B, C, D, K)
Efficiency
> 88 % (for 230 V AC and nominal values)
Setting range of the output voltage (U<sub>Set</sub>)
18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (I<sub>N</sub>)
3.5 A (-25 °C ... 60 °C, U<sub>OUT</sub> = 24 V DC)
POWER BOOST (I<sub>Boost</sub>)
4 A (-25 °C ... 40 °C permanent, U<sub>OUT</sub> = 24 V DC )
Selective Fuse Breaking (I<sub>SFB</sub>)
Magnetic circuit breaker tripping
Derating
60 °C ... 70 °C (2.5 %/K)
Feedback voltage resistance
Protection against overvoltage at the output (OVP)
Control deviation
< 0.1 % (change in input voltage ±10 %)
< 1 % (change in load, static 10 % ... 90 %)
< 2 % (change in load, dynamic 10 % ... 90 %)
Residual ripple
< 50 mV<sub>PP</sub> (with nominal values)
Maximum no-load power dissipation
Power loss nominal load max.
Rise time
< 0.04 s (U<sub>OUT</sub> (10 % ... 90 %))
Connection in parallel
yes, for redundancy and increased capacity
Output description
I<sub>OUT</sub> < I<sub>N</sub>: High signal
Relay contact, U<sub>OUT</sub> > 0.9 x U<sub>N</sub>: Contact closed
U<sub>OUT</sub> > 0.9 x U<sub>N</sub>: High signal
Maximum inrush current
≤ 20 mA (short-circuit-proof)
0.5 A
1 A
Maximum switching voltage