Notes on operation
Separating plate PLC-ATP must be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal blocks in adjacent modules. Potential bridging is then carried out with FBST 8-PLC... or FBST 500....
The PLC-ATP separating plate should be installed for safe isolation between adjacent modules
The system installer must ensure the touch protection of the product (at voltages > 25 V AC/60 V DC). The product is a built-in device without protection against direct contact.
Assembly note
in rows with zero spacing
The PLC-ATP separating plate is required at the start and end of every PLC terminal strip.
Typical input current at UN
Insulation
Safe isolation, reinforced insulation
Date of last data management
Maximum power dissipation for nominal condition
Test voltage (Winding/contact)
4 kV AC (50 Hz, 1 min., winding/contact)
Nominal input voltage U<sub>N</sub>
Input voltage range
20.2 V DC ... 33.6 V DC (20 °C)
Nominal voltage (plugged-in electromechanical relay)
Typical input current at U<sub>N</sub>
Protective circuit
Reverse polarity protection; Polarity protection diode
Surge protection; Freewheeling diode
Operating voltage display
Maximum switching voltage
250 V AC/DC (The separating plate PLC-ATP should be installed for voltages larger than 250 V (L1, L2, L3) between identical terminal blocks in adjacent modules. Potential bridging is then carried out with FBST 8-PLC... or ...FBST 500...)
Minimum switching voltage
Limiting continuous current
10 A (the value is permissible if both connections 13, both connections 14 and both connections BB are bridged)
6 A
Maximum inrush current
130 A (peak, at capacitive load, 230 V AC, 24 μF)
80 A (20 ms)
Interrupting rating (ohmic load) max.
144 W (at 24 V DC)
1500 VA (for 250 V AC)
48 W (at 60 V DC)
50 W (at 110 V DC)
58 W (at 48 V DC)
80 W
85 W (for 250 V DC)
Interrupting rating (ohmic load) max. bridged
240 W (for 24 V DC. The value is permissible if both connections 13, both connections 14 and both connections BB are bridged.)
2500 VA (for 250 V AC. The value is permissible if both connections 13, both connections 14 and both connections BB are bridged.)
Switching capacity
0.2 A (at 110 V, DC13)
0.2 A (at 250 V, DC13)
2 A (at 24 V, DC13)
6 A (at 120 V, AC15)
6 A (at 24 V, AC15)
6 A (at 250 V, AC15)
Conductor cross-section rigid
Conductor cross-section flexible
0.14 mm² ... 2.5 mm²
0.2 mm² ... 2.5 mm² (Single ferrule)
2x 0.5 mm² ... 1 mm² (TWIN ferrule)
Conductor cross-section AWG
Flammability rating according to UL 94 (Housing)
Degree of protection (Relay)