Typical input current at UN
10 mA (At U<sub>N</sub> = 48 V AC)
9.2 mA (At U<sub>N</sub> = 48 V DC)
Mechanical service life
approx. 3x 10<sup>7</sup> cycles
Date of last data management
Maximum power dissipation for nominal condition
Test voltage (Winding/contact)
4 kV AC (50 Hz, 1 min., winding/contact)
Nominal input voltage U<sub>N</sub>
Input voltage range
38.4 V AC/DC ... 60 V AC/DC (20 °C)
Nominal voltage (plugged-in electromechanical relay)
Typical input current at U<sub>N</sub>
10 mA (At U<sub>N</sub> = 48 V AC)
9.2 mA (At U<sub>N</sub> = 48 V DC)
Protective circuit
Bridge rectifier; Bridge rectifier
Operating voltage display
Note
<b>the following values are applicable if a gold layer is destroyed</b>
If the specified maximum values are exceeded, the gold plating is destroyed. The AgNi contact values are then valid for further operation; a reduction in length of service life is to be expected.
Maximum switching voltage
250 V AC/DC
30 V AC
36 V DC
Minimum switching voltage
100 mV (at 10 mA)
5 V (at 100 mA)
Limiting continuous current
Min. switching current
1 mA (24 V)
10 mA (at 12 V)
Short-circuit current
200 A (conditional short-circuit current)
Interrupting rating (ohmic load) max.
1.2 W (at 24 V DC)
140 W (at 24 V DC)
1500 VA (for 250 V AC)
18 W (at 60 V DC)
20 W (at 48 V DC)
23 W (at 110 V DC)
40 W (at 220 V DC)
Conductor cross-section rigid
Conductor cross-section flexible
0.14 mm² ... 2.5 mm²
0.2 mm² ... 2.5 mm² (Single ferrule)
2x 0.5 mm² ... 1 mm² (TWIN ferrule)
Conductor cross-section AWG
Degree of protection (Relay base)
Ambient temperature (operation)
Ambient temperature (storage/transport)
Certificate
CE-compliant
TAE0000196
UKCA-compliant
Identification
EN 60068-2-60
ISA-S71.04. G3 Harsh Group