EMC note
EMC: class A product, see manufacturer's declaration in the download area
Electrical isolation between input and output
Maximum power dissipation for nominal condition
Maximum temperature coefficient
Temperature coefficient, typical
Maximum transmission error
≤ 0.1 % (of final value)
≤ 0.5 % (Without adjustment)
Standards/regulations
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6
EN 61000-6-4
IEC/EN 61010
Supply voltage range
9.6 V DC ... 30 V DC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715)
Max. current consumption
< 20 mA (10 V voltage output with 30 mA load at 30 V DC IN)
< 25 mA (10 V output with 30 mA load at 24 V DC IN)
< 50 mA (10 V voltage output with 30 mA load at 12 V DC IN)
< 65 mA (10 V output with 30 mA load at 9.6 V DC IN)
Power consumption
< 540 mW (at 30 V IN)
< 564 mW (At 12 V IN)
< 600 mW (at 24 V IN)
< 624 mW (at 9.6 V IN)
Configurable/programmable
Max. voltage output signal
10 V DC
2.5 V DC
5 V DC
7.5 V DC
Conductor cross-section rigid
Conductor cross-section flexible
Conductor cross-section AWG
Fire protection for rail vehicles (DIN EN 45545-2) R22
Fire protection for rail vehicles (DIN EN 45545-2) R23
Fire protection for rail vehicles (DIN EN 45545-2) R24
Ambient temperature (operation)
Ambient temperature (storage/transport)
Permissible humidity (operation)
5 % ... 95 % (non-condensing)
Identification
Class I, Div. 2, Groups A, B, C, D T6
Class I, Zone 2, Group IIC
UL 508 Listed
Electromagnetic compatibility
Conformance with EMC directive