EMC note
EMC: class A product, see manufacturer's declaration in the download area
Electrical isolation between input and output
Step response (0–99%)
200 ms (2-conductor)
500 ms (3-conductor)
500 ms (4-conductor)
Maximum temperature coefficient
Transmission error resistance-type sensor
Transmission error resistance thermometer
0.1 % * 350 K / set measuring range; 0.1 % > 350 K (Pt/Ni)
0.3 % * 200 K / set measuring range; 0.3 % > 200 K (Cu)
Standards/regulations
EN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6
EN 61000-6-4
IEC/EN 61010
Supply voltage range
9.6 V DC ... 30 V DC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN 60715)
Typical current consumption
Power consumption
≤ 700 mW (at I<sub>OUT</sub> = 20 mA, 9.6 V DC, load 500 Ω)
Configurable/programmable
Sensor types (RTD) that can be used
Temperature measuring range
-200 °C ... 850 °C (Range depends on sensor type, range can be set freely via software or in increments from -150°C to 850°C via DIP switches)
min. 50 K
Max. permissible overall conductor resistance
Linear resistance measuring range
0 Ω ... 4000 Ω (Minimum measuring span: 10% of the selected measuring range)
Voltage output signal
0 V ... 10 V
0 V ... 5 V
1 V ... 5 V
10 V ... 0 V
Max. voltage output signal
Current output signal
0 mA ... 20 mA
20 mA ... 0 mA
20 mA ... 4 mA
4 mA ... 20 mA
Max. current output signal
Load/output load voltage output
Load/output load current output
Ripple
< 20 mV<sub>PP</sub>
< 20 mV<sub>PP</sub> (at 500 Ω)
Conductor cross-section rigid
Conductor cross-section flexible
Conductor cross-section AWG
Fire protection for rail vehicles (DIN EN 45545-2) R22
Fire protection for rail vehicles (DIN EN 45545-2) R23