Typical input current at UN
Mechanical service life
approx. 10<sup>7</sup> cycles
Date of last data management
Maximum power dissipation for nominal condition
Test voltage (Winding/contact)
2.5 kV<sub>rms</sub> (50 Hz, 1 min., winding/contact)
Test voltage (Contact/contact)
2.5 kV<sub>rms</sub> (50 Hz, 1 min., contact/contact)
Test voltage (N/O contact / N/O contact)
2.5 kV<sub>rms</sub> (50 Hz, 1 min., N/O contact / N/O contact)
Nominal input voltage U<sub>N</sub>
Input voltage range
195.5 V AC ... 253 V AC (20 °C)
Typical input current at U<sub>N</sub>
Typical response time
5 ms ... 25 ms (depending on phase relation)
Typical release time range
5 ms ... 20 ms (depending on phase relation)
Maximum switching voltage
Minimum switching voltage
Limiting continuous current
Maximum inrush current
50 A (20 ms, N/O contacts)
Interrupting rating (ohmic load) max.
183 W (at 220 V DC)
384 W (at 24 V DC)
4000 VA (at 440 V AC)
4000 VA (for 250 V AC)
600 W (at 60 V DC)
660 W (at 110 V DC)
720 W (at 48 V DC)
Switching capacity
1 A (at 120 V, DC13)
1 A (at 220 V, DC13)
1 A (at 24 V, DC13)
1.5 A (at 120 V, AC15)
1.5 A (at 24 V, AC15)
1.5 A (at 240 V, AC15)
Motor load according to UL 508
1/2 HP, 240 V AC (N/O contact)
1/3 HP, 120 V AC (N/O contact)
Ambient temperature (operation)
Ambient temperature (storage/transport)
Identification
EN 60068-2-60
ISA-S71.04. G3 Harsh Group