Control input (configurable) Rem
Output power ON/OFF (SLEEP MODE)
Inrush current integral (I2t)
Default
24 V DC 20 mA 24 V DC for P<sub>Out</sub> < P<sub>N</sub>
24 V DC 20 mA 24 V DC for U<sub>Out</sub> > 0.9 x U<sub>Set</sub>
closed (U<sub>out</sub> > 0.9 U<sub>Set</sub>)
Output power ON (>40 kΩ/24 V DC/open bridge between Rem and SGnd)
Frequency range (fN)
16.7 Hz (acc. to EN 50163)
50 Hz ... 60 Hz -10 % ... +10 %
Setting range of the output voltage (USet)
24 V DC ... 28 V DC (constant capacity)
Nominal input voltage range
100 V AC ... 240 V AC
110 V DC ... 250 V DC
Nominal output current (IN)
Input voltage range
100 V AC ... 240 V AC -15 % ... +10 %
110 V DC ... 250 V DC -18 % ... +40 %
Static Boost (IStat.Boost)
Dynamic Boost (IDyn.Boost)
Selective Fuse Breaking (ISFB)
Typical national grid voltage
POut
> 100 % (LED lights up yellow, output power > 480 W)
> 50 % (LED lights up green, output power > 240 W)
> 75 % (LED lights up green, output power > 360 W)
Voltage type of supply voltage
UOut
< 0.9 x U<sub>Set</sub> (LED flashes green)
> 0.9 x U<sub>Set</sub> (LED lights up green)
Inrush current integral (I<sup>2</sup>t)
Inrush current limitation
AC frequency range
50 Hz ... 60 Hz -10 % ... +10 %
Frequency range (f<sub>N</sub>)
16.7 Hz (acc. to EN 50163)
50 Hz ... 60 Hz -10 % ... +10 %
Mains buffering time
typ. 36 ms (120 V AC)
typ. 36 ms (230 V AC)
Current consumption
2.5 A (250 V DC)
2.7 A (240 V AC)
2.8 A (230 V AC)
5.5 A (120 V AC)
6 A (110 V DC)
6.8 A (100 V AC)
Nominal power consumption
Protective circuit
Transient surge protection; Varistor, gas-filled surge arrester
Input fuse
12 A (slow-blow, internal)
Recommended breaker for input protection
10 A ... 16 A (Characteristic B, C, D, K or comparable)
Discharge current to PE
< 3.5 mA
1.7 mA (264 V AC, 60 Hz)
Efficiency
typ. 92.7 % (120 V AC)
typ. 94.2 % (230 V AC)
Setting range of the output voltage (U<sub>Set</sub>)
24 V DC ... 28 V DC (constant capacity)
Nominal output current (I<sub>N</sub>)
Dynamic Boost (I<sub>Dyn.Boost</sub>)
Selective Fuse Breaking (I<sub>SFB</sub>)
Magnetic circuit breaker tripping
A1...A16 / B2...B13 / C1...C6 / Z1...Z16
Derating
> 60 °C ... 70 °C (2.5 %/K)
Feedback voltage resistance
Protection against overvoltage at the output (OVP)
< 30 V DC (double protection with shut off within 20 ms)
Control deviation
< 0.25 % (change in input voltage ±10 %)
< 0.5 % (Static load change 10 % ... 90 %)
< 2 % (Dynamic load change 10 % ... 90 %, (10 Hz))
Residual ripple
< 30 mV<sub>PP</sub> (with nominal values)
Maximum no-load power dissipation
< 5 W (120 V AC)
< 5 W (230 V AC)
Power loss nominal load max.
< 30 W (230 V AC)
< 38 W (120 V AC)