Inrush current integral (I2t)
Nominal input voltage range
Setting range of the output voltage (USet)
30 V DC ... 56 V DC (> 48 V DC, constant capacity restricted)
Nominal output current (IN)
Selective Fuse Breaking (ISFB)
Voltage type of supply voltage
Inrush current integral (I<sup>2</sup>t)
Current consumption
7 A (48 V, I<sub>BOOST</sub>)
Reverse polarity protection
Nominal power consumption
Protective circuit
Transient surge protection; Varistor
Input fuse
15 A (internal (device protection))
Setting range of the output voltage (U<sub>Set</sub>)
30 V DC ... 56 V DC (> 48 V DC, constant capacity restricted)
Nominal output current (I<sub>N</sub>)
POWER BOOST (I<sub>Boost</sub>)
Selective Fuse Breaking (I<sub>SFB</sub>)
Magnetic circuit breaker tripping
Derating
60 °C ... 70 °C (2.5 %/K)
Feedback voltage resistance
Protection against overvoltage at the output (OVP)
Active current limitation
Control deviation
< 0.1 % (change in input voltage ±10 %)
< 1 % (change in load, static 10 % ... 90 %)
< 2 % (change in load, dynamic 10 % ... 90 %)
Peak switching voltages nominal load
< 10 mV<sub>PP</sub> (20 MHz)
Maximum no-load power dissipation
Power loss nominal load max.
Rise time
< 2 ms (U<sub>OUT</sub> (10 % ... 90 %))
Connection in parallel
yes, for redundancy and increased capacity
Output description
I<sub>OUT</sub> < I<sub>N</sub>: High signal
U<sub>IN</sub> > 38.4 V: high signal
U<sub>OUT</sub> > 0.9 x U<sub>N</sub>: High signal
Maximum inrush current
< 20 mA (short-circuit-proof)
≤ 20 mA (short-circuit-proof)
Connection method
Pluggable screw connection
Conductor cross-section, rigid min.
Conductor cross-section, rigid max.
Conductor cross-section flexible min.
Conductor cross-section flexible max.
Conductor cross-section AWG min.
Conductor cross-section AWG max.