Inrush current integral (I2t)
Nominal input voltage range
Setting range of the output voltage (USet)
18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN)
POWER BOOST (IBoost)
12.5 A (-40 °C ... 40 °C permanent, U<sub>OUT</sub> = 24 V DC)
Selective Fuse Breaking (ISFB)
Voltage type of supply voltage
Inrush current integral (I<sup>2</sup>t)
Current consumption
4.7 A (72 V DC)
5.6 A (60 V DC)
Reverse polarity protection
Nominal power consumption
Protective circuit
Transient surge protection; Varistor
Input fuse
10 A 150 V DC (internal (device protection))
Efficiency
> 91 % (U<sub>IN</sub> 60 V DC / U<sub>OUT</sub> 24 V DC)
> 91 % (U<sub>IN</sub> 72 V DC / U<sub>OUT</sub> 24 V DC)
Setting range of the output voltage (U<sub>Set</sub>)
18 V DC ... 29.5 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (I<sub>N</sub>)
POWER BOOST (I<sub>Boost</sub>)
12.5 A (-40 °C ... 40 °C permanent, U<sub>OUT</sub> = 24 V DC)
Selective Fuse Breaking (I<sub>SFB</sub>)
Magnetic circuit breaker tripping
Derating
60 °C ... 70 °C (2.5 %/K)
Feedback voltage resistance
Protection against overvoltage at the output (OVP)
Active current limitation
Control deviation
< 0.1 % (change in input voltage ±10 %)
< 1 % (change in load, static 10 % ... 90 %)
< 2 % (change in load, dynamic 10 % ... 90 %)
Peak switching voltages nominal load
< 10 mV<sub>PP</sub> (20 MHz)
Maximum no-load power dissipation
4 W (U<sub>IN</sub> 60 V DC)
Power loss nominal load max.
24 W (U<sub>IN</sub> 60 V DC)
Rise time
< 2 ms (U<sub>OUT</sub> (10 % ... 90 %))
Connection in parallel
yes, for redundancy and increased capacity
Fuse protection (secondary side)
electronic
thermal
thermal-magnetic
Output description
I<sub>OUT</sub> < I<sub>N</sub>: High signal
Relay
U<sub>IN</sub> > 19.2 V: High signal
U<sub>OUT</sub> > 0.9 x U<sub>N</sub>: High signal
Maximum inrush current
< 20 mA (short-circuit-proof)
≤ 100 mA
≤ 20 mA (short-circuit-proof)
Conductor cross-section, rigid min.
Conductor cross-section, rigid max.
Conductor cross-section flexible min.