Input voltage range
100 V AC ... 240 V AC -15 % ... +10 %
110 V DC ... 250 V DC
Inrush current integral (I2t)
Voltage type of supply voltage
Dynamic Boost (IDyn.Boost)
Inrush current integral (I<sup>2</sup>t)
Frequency range (f<sub>N</sub>)
Output power POUT (UN, IOUT = IN)
Typical current consumption
1.8 A (110 V DC)
3.3 A (100 V AC)
Input fuse
6.3 A (slow-blow, internal)
Efficiency
typ. 85 % (120 V AC)
typ. 87 % (230 V AC)
typ. 96 % (Battery operation)
Derating
> 60 °C (2.5%/K of P<sub>Out </sub>nom.)
Crest factor
2.7 (120 V AC)
3.2 (230 V AC)
UPS connection in parallel
yes, with diode module uncoupled
Energy storage device connection in parallel
Feedback voltage resistance
Protection against overvoltage at the output (OVP)
Control deviation
< 0.1 % (change in input voltage ±10 %)
< 0.75 % (change in load, static 10 % ... 90 %)
< 1.25 % (Dynamic load change 10 % ... 90 %, 10 Hz)
Output voltage
24 V DC
U<sub>BAT </sub>-0.1 V DC
Output voltage range
18 V DC ... 30 V DC
24 V DC ... 28 V DC (> 24 V constant capacity)
Output current I<sub>N</sub>
Dynamic Boost (I<sub>Dyn.Boost</sub>)
Output power P<sub>OUT</sub> (U<sub>N</sub>, I<sub>OUT</sub> = I<sub>N</sub>)
Maximum no-load power dissipation
Power loss nominal load max.
Nominal voltage U<sub>N</sub>
Charging current (Configurable)
0.2 A ... 1.5 A (-25 °C ... 40 °C)
Charging current (Reduced)
1.5 A ... 0 A (40 °C ... 65 °C)
Charging current (Preset)
Charge characteristic curve
Connection method
MINI-USB Type B
Push-in connection
rigid
0.2 mm² ... 1.5 mm²
0.2 mm² ... 10 mm²
0.2 mm² ... 4 mm²
flexible
0.2 mm² ... 1.5 mm²
0.2 mm² ... 2.5 mm²
0.2 mm² ... 6 mm²
flexible with ferrule without plastic sleeve
0.2 mm² ... 1.5 mm²
0.25 mm² ... 2.5 mm²
0.25 mm² ... 6 mm²
flexible with ferrule with plastic sleeve
0.2 mm² ... 0.75 mm²
0.25 mm² ... 1.5 mm²
0.25 mm² ... 4 mm²
AWG
24 ... 12
24 ... 16
24 ... 8