Max. internal inductance Li
Max. internal capacitance Ci
Max. output current Io
≤ 22.1 mA
≤ 5 mA
≤ 96.5 mA
Max. output power Po
≤ 151 mW
≤ 34.2 mW
≤ 659 mW
Ex ia IIC: Max. external inductivity Lo / Max. external capacitance Co
4 mH / 88 nF
500 mH / 88 nF
500 µH / 85 nF
Ex ia IIB: Max. external inductivity Lo / Max. external capacitance Co
17 mH / 683 nF
2 mH / 360 nF
2 mH / 380 nF
Ex ia IIA: Max. external inductivity Lo / Max. external capacitance Co
100 mH / 540 nF
34 mH / 2280 nF
5 mH / 530 nF
Test voltage (Input/output)
Supply voltage range
24 V AC/DC ... 230 V AC/DC (-20 % ... +10 %, 50 Hz ... 60 Hz)
Current input signal
0 mA ... 20 mA +10 %
4 mA ... 20 mA +10 %
Max. current input signal
Available input sources
Current
Resistance thermometers
Resistance: 30 Ω ... 3000 Ω
Thermocouples
Voltage
Input resistance current input
Transmitter supply voltage
Transmitter supply voltage range
22.8 V ... 27.6 V (No-load)
Transmitter supply current
< 30 mA (Short-circuit and overload protection)
Voltage input signal
-1 V ... 1 V
-10 V ... 10 V
-100 mV ... 100 mV
-30 V ... 30 V
0 V ... 1 V
0 V ... 10 V
0 V ... 5 V
1 V ... 5 V
2 V ... 10 V
Max. voltage input signal
± 12 V (< 1 V)
± 35 V (≥ 1 V)
Input resistance of voltage input
Configurable/programmable
Sensor types (RTD) that can be used
Temperature measuring range
-200 °C ... 1100 °C (Range depends on sensor type, adjustable)
-200 °C ... 2495 °C (Range depends on sensor type, adjustable)
Sensor types that can be used (TC)
J, K, T, N, B, S, R, U. L, C, D
Contact switching type
2 changeover contacts
Transistor
Minimum switching voltage
Maximum switching voltage
230 V AC (3 A)
28 V
30 V DC (3 A)
Current output signal
0 mA ... 20 mA
4 mA ... 20 mA
Max. current output signal
Load/output load current output