Nominal voltage UN
240 V AC (TN-S)
240 V AC (TT)
Maximum continuous operating voltage UC
240 V DC
264 V AC
275 V AC
Type
DIN rail module, two-section, divisible
Protective conductor current IPE
Standby power consumption PC
≤ 26.4 mVA (at U<sub>C</sub>)
≤ 26.4 mVA (at U<sub>REF</sub>)
Surge protection fault message
Optical, remote indicator contact
Reference test voltage UREF
Nominal discharge current In (8/20) µs
Maximum discharge current Imax (8/20) µs
Voltage protection level Up (L-N)
≤ 1.25 kV (at U<sub>OC</sub>)
≤ 1.4 kV (at I<sub>n</sub>)
Connection name
Remote fault indicator contact
Voltage protection level Up (L-PE)
Voltage protection level Up (N-PE)
Operating voltage
125 V DC (200 mA DC)
250 V AC
TOV behavior at UT (L-N)
400 V AC (5 s / withstand mode)
457 V AC (120 min / safe failure mode)
Operating current
0.5 A AC
0.5 A DC (75 V DC)
TOV behavior at UT (L-PE)
1464 V AC (200 ms / safe failure mode)
457 V AC (120 min / withstand mode)
457 V AC (5 s / withstand mode)
TOV behavior at UT (N-PE)
1200 V AC (200 ms / safe failure mode)
Conductor cross-section flexible
Conductor cross-section rigid
Conductor cross-section AWG
Short-circuit current rating ISCCR
0.25 kA DC (Without additional backup fuse in the DC branch wiring)
10 kA AC
5 kA DC (for 20 A gG / B backup fuse)
Residual voltage Ures (L-N)
≤ 1.1 kV (at U<sub>OC</sub> = 4 kV)
≤ 1.15 kV (at 2 kA)
≤ 1.25 kV (at 3 kA)
Depth
74.5 mm (incl. DIN rail 7.5 mm)
Residual voltage Ures (L-PE)
≤ 1.1 kV (at 2 kA)
≤ 1.1 kV (at 3 kA)
≤ 1.2 kV (at U<sub>OC</sub> = 4 kV)
Residual voltage Ures (N-PE)
≤ 1.1 kV (at 2 kA)
≤ 1.1 kV (at 3 kA)
≤ 1.2 kV (at U<sub>OC</sub> = 4 kV)
Pulse discharge current Iimp (10/350) µs (line-line)
Pulse discharge current Iimp (10/350) µs (line-earth)